5.8 CONNECTOR PANEL
Admin Master
Structure
30
31
32
33
34
35
38
37
36
39
30
230 V AC service plugs
31
24 V voltage supply for communication components
32
N conductor terminal block
33
Circuit breakers
34
PE conductor terminal block
35
Surge arrester (for consumer)
36
Network connections (Janitza, STPS, APU)
37
X3/X4 terminals
38
NH00 isolator STPS and consumer
39
X1 through clamps
X3/X4 terminal assignment
37
1
2
3
4
X3: max. 95 mm
2
X4: max. 95 mm
2
1
X3 (+) BatBreaker input terminal to STPS (red)
2
X3 (-) BatBreaker input terminal to STPS (black)
3
X4 (+) APU output terminal to BatBreaker (white)
4
X4 (-) APU output terminal to BatBreaker (blue)
Circuit breaker assignment
1
F3 circuit breaker for heating unit L
2
F3 circuit breaker for heating unit N
3
F4 circuit breaker for air conditioner 1 L
4
F4 circuit breaker for air conditioner 1 N
5
F5 circuit breaker for air conditioner 2 L
6
F5 circuit breaker for air conditioner 2 N
7
F6 RCB / CB service plugs L
8
F6 RCB / CB service plugs N
9
F7 circuit breaker for 24 V voltage supply / IVM
10
F7 spare circuit breaker for router
NH00 isolator assignment
38
4
5
6
1
2
3
1
F1 STPS connection L1 (125 A)
2
F1 STPS connection L2 (125 A)
3
F1 STPS connection L3 (125 A)
4
F2 Outdoor consumer L1 (35 A)
5
F2 Outdoor consumer L2 (35 A)
6
F2 Outdoor consumer L3 (35 A)
X1 through clamp assignment
39
1
2
3
4
5
6
7
8
9
X1: max. 50 mm²
1
AC connection L1
2
AC connection L1
3
AC connection L2
4
AC connection L2
5
AC connection L3
6
AC connection L3
7
AC connection N
8
AC connection N
9
AC connection PE
33
1 2 3 4 5 6 7 8 9 10