40
CommIssIonIng
© TESVOLT We reserve the right to make technical changes! RD.TI.026.E.ENG_Installation_Manual_TSHV70OD_v.A.01 Last revised
07/2020
7
Check and monitor the commissioned components as they start up. Also, check the display on the air
conditioner casing on the inside of the cabinet. On the communication components, check the 24 V volt-
age supply
31
and the
SMA Inverter Manager
P
, SMA Data Manager M
Q
and the switches
O
.
8
You can now commission all the slave storage systems. Proceed in reverse order according to their
position in the master/slave configuration. Start with the last slave in the master/slave configuration
and switch it on using the ON/OFF switch “SWITCH”
17
on the APU HV1000-S.
9
The number of battery modules detected (14 or 16) is shown on the
slave storage system’s display. Confirm the correct number by
tapping twice on the marking
16
next to the display. If the num-
ber of modules displayed is not the same as the actual number,
check the BAT COM wiring. If the error persists, please email ser-
[email protected] or contact the TESVOLT Service Line +49 (0)
3491 8797 - 200. Once commissioning has been completed suc-
cessfully, the status changes to “CAN-FLT”.
10
Switch on the next slave storage system and proceed as follows in steps
4
and
5
, i.e. as for com-
missioning the first slave.
11
Once all of the slave storage systems have been commissioned, the master cabinet can be started. To
do this, press the ON/OFF switch “SWITCH”
17
on the APU HV1000-S.
12
Unlike the slave APUs, the master initially requests the number of
“strings”. The number of strings corresponds to the number of
storage systems in the master/slave configuration (e.g.
slave 1 + slave 2 = three strings). Confirm the correct number by
tapping twice next to the display. In the event of deviations, check
the CAN IN –> CAN OUT cabling, the termination and the addressing.
Then insert the fuses in the slave cabinets. If the error occurs
again, please email [email protected] or contact the TESVOLT
Service Line +49 (0) 3491 8797 - 200.
13
The number of battery modules detected (14 or 16) is now shown
on the master APU’s display. Confirm the correct number by tap-
ping twice. In the event of deviations, check the BAT COM wiring.
If the error continues to occur regardless, please email service@
tesvolt.com or contact the TESVOLT Service Line +49 (0) 3491
8797 - 200.
14
Tap beside the display again to access the next menu item. You
will now be shown the assigned IP address, which must start
with 192.168.4. ….
The IP address is required to commission the STPS.