29
UK
9.3.2 Time-controlled counter reset
►
Select [rTo] and set the requested value (intervals of hours, days or
weeks)�
> The totaliser is reset automatically with the value now set�
Menu EF:
[rTo]
9.3.3 Deactivation of the counter reset
►
Select [rTo] and set OFF�
> The totaliser is only reset after overflow�
Menu EF:
[rTo]
9.4 Settings for temperature monitoring
9.4.1 Analogue signal temperature OUT1 or OUT2
►
Select [SELx] and set TEMP�
►
Select [ASPx] and set the value at which 4 mA is provided�
►
Select [AEPx] and set the value at which 20 mA is provided�
Menu OUTx:
[SELx]
[ASPx]
[AEPx]
9.5 Settings for pressure monitoring
9.5.1 Analogue signal pressure OUT1 or OUT2
►
Select [SELx] and set PRES�
►
Select [ASPx] and set the value at which 4 mA is provided�
►
Select [AEPx] and set the value at which 20 mA is provided�
Menu OUTx:
[SELx]
[ASPx]
[AEPx]