24
7.6 Explanation of the menu
7.6.1 Submenu OUT1 and OUT2
Parameter
Explanation and setting options
SELx
standard unit of measurement for evaluation by OUTx:
FLOW (volumetric flow) or TEMP (temperature) or PRES (pressure)
ASPx
analogue start point for OUTx
AEPx
analogue end point for OUTx
FOUx
response of OUTx in case of an internal fault:
OU = analogue signal goes to 21�5 mA in case of a pressure
measurement error and to 3�5 mA in case of a flow or temperature
measurement error�
On = analogue signal goes to 21�5 mA�
OFF = analogue signal goes to 3�5 mA�
7.6.2 Submenu CFG
Parameter
Explanation and setting options
uni�F
standard unit of measurement for volumetric flow
uni�T
standard unit of measurement for temperature
uni�P
standard unit of measurement for pressure
dAP�F
measured value damping for volumetric flow
dAP�P
measured value damping for pressure
LFC
low flow cut-off
rEF�P
standard pressure to which the measured and display values for volumet-
ric flow refer
rEF�T
standard temperature to which the measured and display values for
volumetric flow refer
coF
Zero-point calibration for pressure measurement� The internal measured
value "0" is shifted by this value�
7.6.3 Submenu MEM
Parameter
Explanation and setting options
Lo�F
min� value of the flow volume measured in the process
Hi�F
max� value of the flow volume measured in the process
Lo�T
min� value of the temperature measured in the process