Temperature Control Units : With ‘LS’ Series Instrument
Page: 40
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
www.Temptek.com
cleaned, place the new
heater gasket onto the
tank mating surface. Coat
the mating surface with a
high temperature gasket
sealant.
10.
Set new heater into tank.
Aligning the bolt pattern
of the heater and tank
flanges.
11.
Replace the 4 heater
mounting bolts. Alternate to the opposite bolt while
tightening.
12.
Reconnect the power cable to the heater terminals. Be
certain to tighten the power cord junction box connector.
Replace the junction box cover and the lift-off cover panel.
D.
When complete, restart the unit.
5.3 PVT
TM
VALVE SERVICE
Remove heater
Figure 5.2D
Содержание VETERAN LS Series
Страница 2: ......
Страница 8: ...Page 8 THIS PAGE INTENTIONALLY BLANK ...
Страница 60: ...Page 60 THIS PAGE INTENTIONALLY BLANK ...
Страница 68: ...Page 68 THIS PAGE INTENTIONALLY BLANK ...
Страница 78: ...Page 78 THIS PAGE INTENTIONALLY BLANK ...
Страница 79: ...END 2013 Temptek INC RE 1 02 13 ...
Страница 80: ......