2.1 GENERAL
A.
All process piping materials such as hose, rigid piping, valves or
filters, used in process water piping circuitry must be rated for
350°F minimum temperature and 200 PSI minimum pressure.
B.
Be certain all process piping materials have the equivalent or larger
diameter of the particular process connection.
Temperature Control Units : With ‘LS’ Series Instrument
Page: 14
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
www.Temptek.com
To process connection:
Connect to “water in” on process manifold
From process connection:
Connect to “water out” on process manifold
Drain connection:
Connect to one of the following:
(Depending on water supply source)
• plant’s open drain
• tower water system return
• chilled water system return
Water supply connection:
Connect to one of the following:
• plant’s city water source
• well water source
• tower water supply
• chilled water supply
2.2
TO AND FROM PROCESS CONNECTIONS
A.
Connect the unit’s To Process port to the Water In port on the
process manifold.
B.
Connect the unit’s From Process port to the Water Out port on the
process manifold.
C.
Please note: Process water piping circuitry should be designed to
avoid an excessive use of elbows and/or lengths of pipe or hose.
If hose is the material of choice, avoid tight twists or curls and
excessive lengths.
D.
Valves and filters may be installed in the process water piping
circuitry to facilitate service and maintenance, provided that such
devices maintain the full inside diameter of the process connection.
If installed, all such devices must be open and clean during unit
operation.
Содержание VETERAN LS Series
Страница 2: ......
Страница 8: ...Page 8 THIS PAGE INTENTIONALLY BLANK ...
Страница 60: ...Page 60 THIS PAGE INTENTIONALLY BLANK ...
Страница 68: ...Page 68 THIS PAGE INTENTIONALLY BLANK ...
Страница 78: ...Page 78 THIS PAGE INTENTIONALLY BLANK ...
Страница 79: ...END 2013 Temptek INC RE 1 02 13 ...
Страница 80: ......