Cellular-Only Wiring (When Communicator is Only Path Used):
This configuration is used when the communicator is set to cellular only mode and is working in a
system that does not involve a Telco connection or a secondary path. In this case, the alarm panel is
connected directly to the communicator, and there is no other communication pathway that is active.
For commercial fire installations, a specific level of link supervision may be required (frequencies of
180 seconds, 5 minutes, or 60 minutes).
In this configuration, the Telco connection is not being used or monitored by the communicator. This
configuration provides for Active communication for Canadian fire systems and P1 line security for
Canadian burglary systems.