NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, OTHER INVOLVED PARTIES
BURGLARY SYSTEM INSTALLATIONS IN CANADA: In order to comply with the requirements in the
Standard for Control Units, Accessories and Receiving Equipment for Intrusion Alarm Systems, ULC-S304,
the communicator must meet these requirements (Security Level I or II):
The TG-7 Cellular Series communicator must be used as a Passive communication system line security level P1
(single communication channel) for Security Level I.
Additionally:
•
Every 24 hours, a test transmission must be sent to the signal receiving centre over the cellular
communication path.
•
The communicator shall be used in conjunction with a ULC or cUL Listed Control Unit/Alarm Panel.
•
STC1 and STC2 shall be connected from the communicator to the control panel and designated for
general trouble conditions.
•
A tamper switch on the communicator shall be connected directly to an input zone on the control panel,
and the zone shall be designated as the Tamper Protection zone. Tamper wires and all other wires
connecting the communicator to the panel shall be in rigid or flexible metal conduit.
•
The PPF panel presence failure feature must be enabled if the wiring distance between the panel and the
communicator is greater than 18m or in different rooms or if the connection is not mechanically protected
in metal conduit; setting is accessible in the online portal.