TG-7 Cellular Series Installation & Operating Guide
12
56053501 Rev A © 2022 Telguard
To begin the factory reset, follow these steps:
•
Power cycle the device. For the first three seconds after power up, all LEDs will be lit solid.
•
While the unit shows this pattern, press and hold the RSSI button. After 15 seconds of button
press, the LEDs will begin to sequentially turn on and off in a cascading pattern, indicating the
factory reset is taking place.
•
Release the RSSI button. After the factory reset concludes, the LEDs will go back to normal
status.
UL and ULC Compliance
The TG-7 Cellular Series communicators are certified as complying with UL and ULC Standards for
Commercial Fire and Commercial Burglary installations. The chart on Page 1 shows the associated UL
and ULC Standards. Certificates of Compliance are available at
UL/ULC Compliance Note:
The alarm panel must also be UL, ULC, or cUL Listed for commercial
fire and/or commercial burglary use as appropriate
.
ULC Compliance Notes:
•
For Commercial Fire installations in Canada, the radio frequency warning label (supplied)
must be affixed to the outside front cover of the communicator to maintain compliance.
•
Communicator is suitable for Active communication in fire installations (ULC -S559) and
for Passive Level 1 (P1) Line Security in burglary installations (ULC-S304).