background image

 

 

TBD-8100 

© 2017

 

– Telefire Fire & Gas Detectors Ltd 

 

Revision 1.00   November 2017 

 

– Page 10 of 10 – 

Specification 

Operating Range 

One prism .............................................................. 8 to 50 meters 
Two prisms ............................................................ 50 to 75 meters 
Four prisms ............................................................ 75 to 100 meters 

Maximum detection area ............................................... 1,800 m

2

 

Prism 

Dimensions (W / H / D) .......................................... 100 / 100 / 10 mm 
Weight ................................................................... 75 g 

Detector dimensions (W / H / D).................................... 76 / 99 / 144 mm 

Detector weight ............................................................. 450 gr. 

Operating Temperature range ....................................... -25°C 

– +55°C  

Relative Humidity Range .............................................. 10% 

– 93% non-condensing 

Nominal voltage supply ................................................. 24Vdc 

Maximum current consumption (24Vdc)  

Quiescence or Alarm State .................................... 20mA 
during calibration.................................................... 50mA 

Local Indication 

normal status: HL4 LED flashes for 0.3 seconds once every 4 seconds 
Alarm: HL4 LED constantly lit 
Fault: The HL4 LED flashes every second 

Error Message: 

You can Figure out the type of fault by watching the combination of the HL1, HL2 
and HL3 LED flashes, while the DIP SW 5 switch is raised. 

Outputs ......................................................................... 2 

Alarm output: Activated during 

each alarm situation until “Return” is implemented 

Fault output: activated during a fault until it is repaired 

All values are nominal.  Specifications are subject to change without prior notice 

Certification 

Telefire’s TBD-8100 Conventional Beam Detector has the following approvals: 

 

SI 1220 Approved 

 

GOST Approved 

 

Содержание TBD-8100

Страница 1: ...nal Beam Detector Technical Manual TELEFIRE FIRE GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel 972 3 970 0400 Fax 972 3 921 1816 eMail info telefire co il Web www telefire co il TBD 8100...

Страница 2: ...72 guideline and UL standards and Fault as used in EN 54 standards are used interchangeably throughout this manual i Note Do not install operate and maintain this product before fully reading this man...

Страница 3: ...7000 GUARD 7 and ADR 3000 Analog Addressable Control Panel when used with an ADR 712 ADR 718 or ADR 812A Input module 3 Installation Planning of quantity and location of detectors shall be done accor...

Страница 4: ...om the addressable control panel or whenever the total current consumption of all NACs exceeds the capability of the addressable control panel s 24Vdc output 3 1 4 Cabling planning shielded cables It...

Страница 5: ...e detection coverage on each side of the beam is 9 meters maximum Place the detector up to 9 meters from the wall or 18 meters from the next similar parallel detector under a flat ceiling i Note Insta...

Страница 6: ...o the zone input in the control panel or to the addressable input assembly use a model TRA 1B adapter see Figure 3 Figure 3 Connecting to the zone input in a control panel or to an addressable assembl...

Страница 7: ...the detector s signal strength amplification and type of fault the letter F appears in one of the screen s locations a More than 50 dust accumulation on the detector b More than 90 dust accumulation o...

Страница 8: ...ects to the detector via two conductors Connect the optional indicator module to the detector as described in the drawing Figure 6 Connection of an Optional TBD 8100R Indicator Assembly to the Detecto...

Страница 9: ...ltage supplied to the detector 4 If the number of lit LEDs starts decreasing you are moving away from the optimum direction Retract until you reach a maximum number of lit LEDs 5 Measure the voltage b...

Страница 10: ...less than 10 m there is a need to attach the black patch supplied with the detector onto the transmitter s lenses The detector would signal by lighting up the red led during the initial adjustment tha...

Страница 11: ...70 of the prism and induce an alarm This action can also be carried out by bringing a magnet near the display LED in the optional TBD 8100R module provided the LED is connected to the detector 7 Ensur...

Страница 12: ...e or Alarm State 20mA during calibration 50mA Local Indication normal status HL4 LED flashes for 0 3 seconds once every 4 seconds Alarm HL4 LED constantly lit Fault The HL4 LED flashes every second Er...

Отзывы: