TBD-8100 

© 2017

 

– Telefire Fire & Gas Detectors Ltd 

 

Revision 1.00   November 2017 

 

– Page 3 of 10 – 

In order to decrease detection time, a proper positioning of the detector is most 
important. 

Based on experience, it is well known that smoke rising from a fire does not go straight 
upwards, but tends to flow sideways; as a result of air flows and the effect of 
temperature gradients among the various air layers, the smoke creates a "mushroom" 
shape at a certain elevation. 

The time interval between the actual time that the fire started and the time that the 
smoke detector alarm sets off depends upon the location and elevation of the beam 
detector, the detection zone, the amount of smoke emitted, the ceiling's shape and the 
ventilation. 

The detection coverage on each side of the beam is 9 meters maximum.  Place the 
detector up to 9 meters from the wall, or 18 meters from the next, similar, parallel 
detector, under a flat ceiling. 

 

   Note    

Install the detector horizontally with the red light down on the right side. 

 

 

Figure 1  Placing the Detectors 

Commonly, rising smoke tends to spread sideways before it reaches the ceiling because 
a layer of hot air near the ceiling prevents the smoke’s further rise.  Therefore, the 
detector should be installed on the building’s wall, at least 50 cm but no more than 1 
meter below the ceiling in order to comply with the UL 268 / NFPA 72 and the SI 1220-3 
2014 edition. 

 

   Note    

Measure the wiring to ensure there are no shorts before connecting the wiring 
to the control panel. 

Connecting or adding inputs, outputs, and extinguishing devices shall be 
done when all power to the control power is disconnected (AC and batteries 
disconnected). 

 

Содержание TBD-8100

Страница 1: ...nal Beam Detector Technical Manual TELEFIRE FIRE GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel 972 3 970 0400 Fax 972 3 921 1816 eMail info telefire co il Web www telefire co il TBD 8100...

Страница 2: ...72 guideline and UL standards and Fault as used in EN 54 standards are used interchangeably throughout this manual i Note Do not install operate and maintain this product before fully reading this man...

Страница 3: ...7000 GUARD 7 and ADR 3000 Analog Addressable Control Panel when used with an ADR 712 ADR 718 or ADR 812A Input module 3 Installation Planning of quantity and location of detectors shall be done accor...

Страница 4: ...om the addressable control panel or whenever the total current consumption of all NACs exceeds the capability of the addressable control panel s 24Vdc output 3 1 4 Cabling planning shielded cables It...

Страница 5: ...e detection coverage on each side of the beam is 9 meters maximum Place the detector up to 9 meters from the wall or 18 meters from the next similar parallel detector under a flat ceiling i Note Insta...

Страница 6: ...o the zone input in the control panel or to the addressable input assembly use a model TRA 1B adapter see Figure 3 Figure 3 Connecting to the zone input in a control panel or to an addressable assembl...

Страница 7: ...the detector s signal strength amplification and type of fault the letter F appears in one of the screen s locations a More than 50 dust accumulation on the detector b More than 90 dust accumulation o...

Страница 8: ...ects to the detector via two conductors Connect the optional indicator module to the detector as described in the drawing Figure 6 Connection of an Optional TBD 8100R Indicator Assembly to the Detecto...

Страница 9: ...ltage supplied to the detector 4 If the number of lit LEDs starts decreasing you are moving away from the optimum direction Retract until you reach a maximum number of lit LEDs 5 Measure the voltage b...

Страница 10: ...less than 10 m there is a need to attach the black patch supplied with the detector onto the transmitter s lenses The detector would signal by lighting up the red led during the initial adjustment tha...

Страница 11: ...70 of the prism and induce an alarm This action can also be carried out by bringing a magnet near the display LED in the optional TBD 8100R module provided the LED is connected to the detector 7 Ensur...

Страница 12: ...e or Alarm State 20mA during calibration 50mA Local Indication normal status HL4 LED flashes for 0 3 seconds once every 4 seconds Alarm HL4 LED constantly lit Fault The HL4 LED flashes every second Er...