background image

 

 

TBD-8100 

© 2017

 

– Telefire Fire & Gas Detectors Ltd 

 

Revision 1.00   November 2017 

 

– Page 2 of 10 – 

Table 1 

Wiring Characteristics’ influence on System Performance 

Use a two-wire cable 

– it is recommended to use a twisted pair cable of 18 – 12 AWG.  

Refer to the following table for maximum branch length per gives cable cross-section.  
Use a shielded twisted-pair when connecting between buildings. 

3.1.2  Cabling Planning 

– control panel zone or input module IDC 

Use a standard two-conductor cable with each conductor having a cross section of 0.8 to 
3.3 mm

2

. Maximum loop resis

tance: 50Ω. 

Table 2 specifies the maximum allowable length of cable, based on the cable’s cross 
section 

Cable Type 

Cross Section 

(mm

2

Detection Line Maximum Length for a 

given Cross Section 

AWG 18 

0.8 mm

2

 

1,200 m 

AWG 16 

1.3 mm

2

 

1,900 m 

AWG 14 

2.1 mm

2

 

3,000 m 

AWG 12 

3.3 mm

2

 

4,800 m 

Table 2 

Maximum Length for an Input Line 

3.1.3  Cabling Planning 

– 24Vdc Supply 

The module requires 24Vdc from the addressable control panel or an auxiliary power 
supply such as the TPS-74A OR TPS-34A. 

Use an auxiliary power supply whenever the module is installed a long distance from the 
addressable control panel or whenever the total current consumption of all NACs 
exceeds the capability of the addressable control panel's 24Vdc output. 

3.1.4  Cabling planning 

– shielded cables 

It is recommended to avoid wiring outside buildings due to a risk of lightning strikes.  If 
required, it is mandatory to use shielded cables.  The shielding must be grounded via the 
control panel grounding terminals. 

3.2 

Installation 

– Prior to Detector Positioning 

3.2.1  Control Panel Detector Configuration 

– Addressable Control 

Panels 

Configure the input addresses of the ADR-712, ADR-718, or ADR-812A as Input Circuit.  
Please refer to the control panel’s technical instructions for further details concerning 
device programming. 

3.2.2  Input configuration in a control panel (TSA-1000 only) 

Ensure that the input, to which the detector is connected, is configured at the panel as a 
type D input (regular detectors zone).  Please refer to the TSA-1000 technical manual for 
a detailed explanation concerning the mode of configuring the various types of inputs. 

3.3 

Installation 

– Placing the Detector 

The TBD-8100 is designed to protect indoor fire risk areas, except environments where 
smoke, steam, dust, or corrosive gasses are present under normal conditions. 

Observe NFPA 72 guidelines and local fire codes when installing the detectors. 

Содержание TBD-8100

Страница 1: ...nal Beam Detector Technical Manual TELEFIRE FIRE GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel 972 3 970 0400 Fax 972 3 921 1816 eMail info telefire co il Web www telefire co il TBD 8100...

Страница 2: ...72 guideline and UL standards and Fault as used in EN 54 standards are used interchangeably throughout this manual i Note Do not install operate and maintain this product before fully reading this man...

Страница 3: ...7000 GUARD 7 and ADR 3000 Analog Addressable Control Panel when used with an ADR 712 ADR 718 or ADR 812A Input module 3 Installation Planning of quantity and location of detectors shall be done accor...

Страница 4: ...om the addressable control panel or whenever the total current consumption of all NACs exceeds the capability of the addressable control panel s 24Vdc output 3 1 4 Cabling planning shielded cables It...

Страница 5: ...e detection coverage on each side of the beam is 9 meters maximum Place the detector up to 9 meters from the wall or 18 meters from the next similar parallel detector under a flat ceiling i Note Insta...

Страница 6: ...o the zone input in the control panel or to the addressable input assembly use a model TRA 1B adapter see Figure 3 Figure 3 Connecting to the zone input in a control panel or to an addressable assembl...

Страница 7: ...the detector s signal strength amplification and type of fault the letter F appears in one of the screen s locations a More than 50 dust accumulation on the detector b More than 90 dust accumulation o...

Страница 8: ...ects to the detector via two conductors Connect the optional indicator module to the detector as described in the drawing Figure 6 Connection of an Optional TBD 8100R Indicator Assembly to the Detecto...

Страница 9: ...ltage supplied to the detector 4 If the number of lit LEDs starts decreasing you are moving away from the optimum direction Retract until you reach a maximum number of lit LEDs 5 Measure the voltage b...

Страница 10: ...less than 10 m there is a need to attach the black patch supplied with the detector onto the transmitter s lenses The detector would signal by lighting up the red led during the initial adjustment tha...

Страница 11: ...70 of the prism and induce an alarm This action can also be carried out by bringing a magnet near the display LED in the optional TBD 8100R module provided the LED is connected to the detector 7 Ensur...

Страница 12: ...e or Alarm State 20mA during calibration 50mA Local Indication normal status HL4 LED flashes for 0 3 seconds once every 4 seconds Alarm HL4 LED constantly lit Fault The HL4 LED flashes every second Er...

Отзывы: