background image

 

 

TBD-8100 

© 2017

 

– Telefire Fire & Gas Detectors Ltd 

 

Revision 1.00   November 2017 

 

– Page 1 of 10 – 

Introduction 

The TBD-8100 Beam Detector is comprised of an optical transmitter and a receiver 
within the same device. 

The transmitter sends out an invisible infrared beam, which is reflected by a prism 
mirror; the mirror is placed on the opposite wall, facing the transmitter in a manner that 
nothing blocks the beam’s path from one side to the other.  The optical receiver monitors 
the intensity of the reflected beam. 

The detector can detect up to 9 meters on each side, 18 meters altogether. 

The TDB-8100 detectors can be installed at three distance ranges: 

 

8 to 50 meters (one prism) 

 

50 to 75 meters (two prisms) 

 

75 to 100 meters (four prisms) 

Compatibility 

The TBD-8100 is compatible with the following control panels: 

 

All TSA-1000 models and TSA-1000X 

 

TSA-200, TSA-240, TSA-200XT, TSA-240 XT, and TSA-200X 

 

ADR-7000, SAVER-7000, GUARD-7, and ADR-3000 Analog Addressable Control 
Panel when used with an ADR-712, ADR-718, or ADR-812A Input module. 

Installation 

Planning of quantity and location of detectors shall be done according to the local codes 
and regulations and in accordance to the planning consultant's requirements. 

   Note    

Notify the operator or the security personnel that the system will be temporary 
disconnected before adding devices to the control panel.  

All connections shall be done when power sources are disconnected. 

 

3.1 

Pre-installation planning 

3.1.1  Cabling Planning 

– Wire Characteristics' Effect 

Cable type selection and wiring shall be done according to local regulations. 

System connections shall be done when power sources are disconnected.  
Changing/installing electric activation modules shall be done after the system is in 
quiescence state (push buttons and detectors in normal state). 

The following table shows the effect of wiring characteristics on system performance: 

Characteristic 

Effect on Input Lines 

Electric Resistance 

Minimal 

Capacitance 

No affect 

Inductance 

Minimal 

Mechanical Strength 

High 

Содержание TBD-8100

Страница 1: ...nal Beam Detector Technical Manual TELEFIRE FIRE GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel 972 3 970 0400 Fax 972 3 921 1816 eMail info telefire co il Web www telefire co il TBD 8100...

Страница 2: ...72 guideline and UL standards and Fault as used in EN 54 standards are used interchangeably throughout this manual i Note Do not install operate and maintain this product before fully reading this man...

Страница 3: ...7000 GUARD 7 and ADR 3000 Analog Addressable Control Panel when used with an ADR 712 ADR 718 or ADR 812A Input module 3 Installation Planning of quantity and location of detectors shall be done accor...

Страница 4: ...om the addressable control panel or whenever the total current consumption of all NACs exceeds the capability of the addressable control panel s 24Vdc output 3 1 4 Cabling planning shielded cables It...

Страница 5: ...e detection coverage on each side of the beam is 9 meters maximum Place the detector up to 9 meters from the wall or 18 meters from the next similar parallel detector under a flat ceiling i Note Insta...

Страница 6: ...o the zone input in the control panel or to the addressable input assembly use a model TRA 1B adapter see Figure 3 Figure 3 Connecting to the zone input in a control panel or to an addressable assembl...

Страница 7: ...the detector s signal strength amplification and type of fault the letter F appears in one of the screen s locations a More than 50 dust accumulation on the detector b More than 90 dust accumulation o...

Страница 8: ...ects to the detector via two conductors Connect the optional indicator module to the detector as described in the drawing Figure 6 Connection of an Optional TBD 8100R Indicator Assembly to the Detecto...

Страница 9: ...ltage supplied to the detector 4 If the number of lit LEDs starts decreasing you are moving away from the optimum direction Retract until you reach a maximum number of lit LEDs 5 Measure the voltage b...

Страница 10: ...less than 10 m there is a need to attach the black patch supplied with the detector onto the transmitter s lenses The detector would signal by lighting up the red led during the initial adjustment tha...

Страница 11: ...70 of the prism and induce an alarm This action can also be carried out by bringing a magnet near the display LED in the optional TBD 8100R module provided the LED is connected to the detector 7 Ensur...

Страница 12: ...e or Alarm State 20mA during calibration 50mA Local Indication normal status HL4 LED flashes for 0 3 seconds once every 4 seconds Alarm HL4 LED constantly lit Fault The HL4 LED flashes every second Er...

Отзывы: