background image

 

 

TBD-8100 

© 2017

 

– Telefire Fire & Gas Detectors Ltd 

 

Revision 1.00   November 2017 

 

– Page 9 of 10 – 

3.5 

Testing the Detectors in the Field after Installation 

 

   Note    

Ensure that the control panel is in walk test mode before testing the 
detectors. 

 

1.  Execute the detector field-test: 

2.  Cover the prism with a non-transparent material (cardboard) 

3.  Ensure that the detector does not enter a fault status for a period of 5 seconds, and 

after 20 seconds the control panel indicates a fault 

4. 

Verify that the detector’s red LED flashes every 1 second 

5.  Once the cardboard has been removed from the prism, verify, that the detector 

returns to normal operation and the red LED flashes once every 5 seconds 

6.  Cover 70% of the prism, and induce an alarm 

This action can also be carried out by bringing a magnet near the display LED in the 
optional TBD-8100R module, provided the LED is connected to the detector 

7.  Ensure that the detector is programmed in the appropriate matrices as specified by 

the planning consultant. 

3.6 

Troubleshooting 

 

Fault 

Possible cause 

Action 

The red LED flashes every 
second. 

The voltage supplied to the 
detector is not in the 
allowed range (8-28V). 

Check and correct the 
voltage feeding the 
detector. 

All green LEDs are flashing 
(see Figure 2).   

The signal emitted by the 
transmitter is too strong 

Attach the black round 
patch (supplied with the 
detector) to the transmitter. 

The red LED is lit 
continuously. 

The transmitter does not 
emit a signal. 

Adjust the detector per 
section 3.4   

The green LEDs are not on.  No power to the detector. 

Check the voltage at points 
1-2 (24Vdc) in the detector. 

 

Содержание TBD-8100

Страница 1: ...nal Beam Detector Technical Manual TELEFIRE FIRE GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel 972 3 970 0400 Fax 972 3 921 1816 eMail info telefire co il Web www telefire co il TBD 8100...

Страница 2: ...72 guideline and UL standards and Fault as used in EN 54 standards are used interchangeably throughout this manual i Note Do not install operate and maintain this product before fully reading this man...

Страница 3: ...7000 GUARD 7 and ADR 3000 Analog Addressable Control Panel when used with an ADR 712 ADR 718 or ADR 812A Input module 3 Installation Planning of quantity and location of detectors shall be done accor...

Страница 4: ...om the addressable control panel or whenever the total current consumption of all NACs exceeds the capability of the addressable control panel s 24Vdc output 3 1 4 Cabling planning shielded cables It...

Страница 5: ...e detection coverage on each side of the beam is 9 meters maximum Place the detector up to 9 meters from the wall or 18 meters from the next similar parallel detector under a flat ceiling i Note Insta...

Страница 6: ...o the zone input in the control panel or to the addressable input assembly use a model TRA 1B adapter see Figure 3 Figure 3 Connecting to the zone input in a control panel or to an addressable assembl...

Страница 7: ...the detector s signal strength amplification and type of fault the letter F appears in one of the screen s locations a More than 50 dust accumulation on the detector b More than 90 dust accumulation o...

Страница 8: ...ects to the detector via two conductors Connect the optional indicator module to the detector as described in the drawing Figure 6 Connection of an Optional TBD 8100R Indicator Assembly to the Detecto...

Страница 9: ...ltage supplied to the detector 4 If the number of lit LEDs starts decreasing you are moving away from the optimum direction Retract until you reach a maximum number of lit LEDs 5 Measure the voltage b...

Страница 10: ...less than 10 m there is a need to attach the black patch supplied with the detector onto the transmitter s lenses The detector would signal by lighting up the red led during the initial adjustment tha...

Страница 11: ...70 of the prism and induce an alarm This action can also be carried out by bringing a magnet near the display LED in the optional TBD 8100R module provided the LED is connected to the detector 7 Ensur...

Страница 12: ...e or Alarm State 20mA during calibration 50mA Local Indication normal status HL4 LED flashes for 0 3 seconds once every 4 seconds Alarm HL4 LED constantly lit Fault The HL4 LED flashes every second Er...

Отзывы: