INS369 CBU-HBWD IP66
CBU-HBWD IP66
IP66 Rated Ceiling High Bay (Wide) Passive
Infra Red (PIR) Occupancy Detector & Photocell
Input: 220-240 Vac 50Hz
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
NOTE: CBU-HBWD IP66 is only compatible to work with CASAMBI enable equipment
This CBU-HBWD IP66 High Bay
(Narrow Detection) Lighting Control
has an IP66 rated weatherproof
enclosure and can be ceiling
mounted. Confi gurable via the free
to download Casambi APP on
Google Play or Apple APP Store.
INSTALLATION
To be installed by a competent person with
reference to BS 7671 or equivalent local standards.
If in doubt consult a qualifi ed electrician.
• Plan where the CBU-HBWD IP66 is to be
located (see diagram 1). Switch off supply and
check for hidden cables and pipes.
• Remove the front cover by quarter turning the
four quick release fasteners to the ‘0’ position
(see diagram 4 overleaf).
• Mount the back section of the mounting box in
the required location via the 4 corner holes.
• Thread mains cable carefully through the
required membrane entry point.
• Unclip the internal back plate. Remove the
required knock out if replacing the optional
internal back plate.
• Thread mains cable into the unit. The CBU-
HBWD IP66 should be connected as shown in
diagram 2:
L - Live in. N - Neutral in.
• Reclip the internal back plate if required.
• Replace the front cover ensuring the quick
release fasteners are secured in the ‘1’ position.
OPERATION
To check the operation of the CBU-HBWD IP66:
• Turn on the supply then after 20 seconds if the
sensor has recognised movement of a person
within its zone of detection the integral red LED
on CBU-HBWD IP66 will stay illuminated for 4
seconds before the red LED turns off.
• Thereafter, every time movement is detected by
CBU-HBWD IP66 the integral red LED will stay
illuminated for 4 seconds.
The control also features adjustable time out (time
lag) control and daylight threshold control which
are confi gured by the Casambi APP.
PRECAUTIONS
• Do not place the CBU-HBWD IP66 near heat
sources, fans or in ventilated ceiling voids.
• CBU-HBWD IP66 can be wired in parallel
(sharing the same Live and Neutral).
• Do not place close to, or positioned such
that, any light source points directly into the
CBU-HBWD IP66.
• Ensure wires and cables are securely held within
the connection terminals.
• The CBU-HBWD IP66 should be protected by a
5 or 6 Ampere mcb or fuse.
•
Disconnect the CBU-HBWD IP66 from the
circuit before performing insulation testing
of the wiring circuit.
DIAGRAM 1
TECHNICAL DETAILS
INPUT
Voltage:
220 - 240Vac
Frequency:
50Hz
Max. mains current:
0.05A
Standby current:
0.05A
RADIO TRANSCEIVER
Operating frequencies: 2.4... 2,483 GHz
Max. output power:
+4 dBm
LUX PARAMETERS
Range:
5 - 2000 lux
OPERATING CONDITIONS
Note: The temperature difference between the
detection target and the background must be
at least 4 °C.
Max. case
temperature:
+70 °C
Storage temperature:
-25... +75 °C
Max. relative humidity:
0... 80%, non cond.
CONNECTORS
Terminal block
Wire size:
0.5mm
2
- 2.5mm
2
solid or stranded
Wire strip length:
6-7mm
Tightening torque:
0,4 Nm/4 Kgf.cm
MECHANICAL DATA
Dimensions:
110mm x 110mm x
73mm
Weight:
255g (unpacked)
Degree of protection:
IP66
Protection class:
Built-in Class 2
Material (casing)
Flame-retardant
polycarbonate/
Polypropylene.
Finish / Colour
Matt /Grey (RAL 7035)
Protection class:
Built-in Class 2
CONFORMITY AND STANDARDS
EMC emission:
EN60669-2-1:2004
inc. A12:2010
EMC immunity:
EN60669-2-1:2004
inc. A12:2010
Safety:
EN60669-2-1:2004
inc. A12:2010
Environment:
Complies with WEEE
and RoHS directives
5 YEAR WARRANTY
CBU-HBWD IP66 comes with a 5 year
warranty from the date of manufacture
and is CE marked.
N
L
N
L
230Vac
5A or 6A MCB
or fuse
L - Live in. N - Neutral in.
Two neutral and two live terminals
are available for easy ‘loop in’ and
‘loop out’ connection.
N
L
DIAGRAM 2
Suggested typical wiring
DIAGRAM 3
plan
side
110
110
73
Up to
28m diameter
Mounting height
up to 14m
Perspective view -
ceiling mounted