MULTIFLAME DF-TV7
OPTICAL FLAME DETECTOR
OPERATING MANUAL
40
NOSP17662
Revision 03
State of the relays:
Each relay can be configured:
•
Normally not-energized
•
Normally energized
Factory setting:
•
Relay 1: normally energized, activated by any fault or inhibition
•
Relay 2: normally not energized, activated on alarm levels
•
Relay 3: normally not energized, activated on alarm levels
Contacts are then described as below
:
Detector status
Relay 1
“Fault”
Relay 2
“Alarm”
Relay 3
“Alarm”
Normal
(no alarm, no fault, no
inhibition and detector
powered)
C1-T1 closed
C1-R1 open
C2-T2 open
C2-R2 closed
C3-T3 open
C3-R3 closed
Pre-Alarm, UV / IR
detection (*)
C1-T1 closed
C1-R1 open
C2-T2 open
C2-R2 closed
C3-T3 open
C3-R3 closed
Alarm
C1-T1 closed
C1-R1 open
C2-T2 closed
C2-R2 open
C3-T3 closed
C3-R3 open
Fault, UV, IR detection
fault or inhibition
C1-T1 open
C1-R1 closed
C2-T2 open
C2-R2 closed
C3-T3 open
C3-R3 closed
Maintenance Inhibition
(during maintenance
mode)
Depend of configuration. See chapter 6.2
Power loss
C1-T1 open
C1-R1 closed
C2-T2 open
C2-R2 closed
C3-T3 open
C3-R3 closed
(*) Available when the detector is in expertise mode
Содержание Everywhereyoulook MultiFlame DF-TV7
Страница 20: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 14 NOSP17662 Revision 03...
Страница 34: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 28 NOSP17662 Revision 03...
Страница 56: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 50 NOSP17662 Revision 03...
Страница 59: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 53 10 Conformity certificate...
Страница 60: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 54 NOSP17662 Revision 03...
Страница 61: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 55...
Страница 62: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 56 NOSP17662 Revision 03...
Страница 63: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 57...