MULTIFLAME DF-TV7
OPTICAL FLAME DETECTOR
OPERATING MANUAL
NOSP17662
Revision 03
41
Activation of the relays:
Each relay can be activated on one or several following conditions:
•
IR detection (expertise mode only)
•
UV detection (expertise mode only)
•
Pre-alarm (expertise mode only)
•
Alarm
•
UV detection fault
•
IR detection fault
•
On all fault
•
Inhibition
Maintenance inhibition:
Maintenance inhibition can be configured in « frozen » mode (factory setting) or « free » mode.
•
In « frozen» mode, the outputs (current and relay) remain in their previous state.
For example, if the device displays a fault (2.0 mA), it will remain in this mode during the
inhibition.
•
If the device is configured in « free » mode, the current output will remain at the same level
than the permanent inhibition
Current protocol configuration :
This menu gives access to the settings of the analog output (4-20 mA or 0-22 mA) and the optical
fault value (1.5 mA , 2 mA or 3 mA).
For a digital detector:
•
the configuration data’s (label, zone and alarms) cannot be modified.
•
the alarm menu is not available
6.9
The maintenance menu [MAIN]
6.9.1
Test sub-menu
The maintenance menu handles tests on the detector:
•
Flame simulation using the integrated test lamps
•
Detection tests using the LT15 test lamp or a test fire
•
Relay output and LED tests
Entering the test menu enables the temporary maintenance inhibition mode.
Without any manual intervention, the sensor come back to normal mode after 10 minutes.
Содержание Everywhereyoulook MultiFlame DF-TV7
Страница 20: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 14 NOSP17662 Revision 03...
Страница 34: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 28 NOSP17662 Revision 03...
Страница 56: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 50 NOSP17662 Revision 03...
Страница 59: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 53 10 Conformity certificate...
Страница 60: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 54 NOSP17662 Revision 03...
Страница 61: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 55...
Страница 62: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 56 NOSP17662 Revision 03...
Страница 63: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 57...