Chapter 3: Frame Installation
3.1 Installation Considerations
ALERT! Only qualified technicians may install and maintain this product.
ALERT! Do not stand on utility or fiber cable troughs at the base of ADFs.
3.1.1 Location & Space
The Main ADF and Interbay Storage Panel require space in front and at rear for access to cabling. Refer to
Figure 25, below. Choose a location in compliance with local operating company requirements.
Telect, Inc. • USA +1.509.926.6000 • 52.33.3836.37.52
www.telect.com • © 2010 Telect, Inc., All Rights Reserved, 119736-4
Page 3-27
Chapter 3: Frame Installation
Advanced Distribution Frame (ADF) Systems
3.1 Installation Considerations
ALERT
!
ALERT! Only qualified technicians may install and maintain this product.
ALERT! Do not stand on utility or fiber cable troughs at the base of ADFs.
3.1.1 Location & Space
The Main ADF and InterBay Storage Panel require space in front and at rear for access to
cabling. Refer to Figure 25, below. Choose a location in compliance with local operating
company requirements.
Rear Aisle Access
Upper ADF Trough Junction
Lower ADF Trough Junction
ADF ISP
ADF ISP
Main ADF
Main ADF
17.5 mm, hole dia. for allthread mounting of CMS or ladder rack
Reserve Area Above
for IFC Drop
M5 Holes for Grounding
Ground Lug and #6 AWG*
Reserve Area Above
for Patch Cord Drop
(1 GND per Main ADF)
End Panel
Figure 25 - Installation Location
3.1.2 Tools & Equipment
The following tools are required for installing ADFs:
• 18-mm (or 23/32 in.) masonry bit
• 40 N
•
m torque wrench with a 19 mm box or open end. (A 19 mm socket can be used if the
socket is at least 54 mm deep.)
• Broadblade screwdriver (~8 mm or
5
/16 in. blade width)
• Horizontal or plumb level (optional)
Figure 25 - Installation Location
3.1.2 Tools & Equipment
The following tools are required for installing ADFs:
• 18mm (or 23/32 in.) masonry bit
• 40 N•m torque wrench with a 19 mm box or open end (19mm socket can be used if the socket is at least 54
mm deep)
• Broad blade screwdriver (~8 mm or 5/16 in. blade width)
• Horizontal or plumb level (optional)
• Isolation pad (if required at base of frame)
• # 1 or # 2 Phillips screwdrivers (screwdrivers for cross-recessed screws) for attaching lower
trough junctions