24
3-rd item
for SIM 2
Er
Х
Error when establishing communication with the
base station.
0 … 9
– error code (descriptions are listed in the
table 1 on page 25)
For HE
8
possible
values for
2-nd and
3-rd
items
«_»
AL is not assigned to ES
R
«
Norm
»
(ready to arm)
status for all ALs (except
«fire heat double-event»).
AL resistance within
3,0 to 5,0 kOhm
.
For AL of
«fire heat double-event» type means that
only one detector
is in fire status
f
«
Failure
»
status.
Resistance ranges for ALs of different types are
various. For details see manual integrated into
Setup
Module
of MSS software
W
AL resistance within
1,5 to 3,0 kOhm
.
For AL of «fire combined double-event» type means
that
only one detector
is in fire status.
For AL of «fire heat double-event» type indicates
«
Normal
» status and
readiness
to be armed
F
«
Fire
» status:
- AL resistance within
5,0 to 12 kOhm
for all AL of
«fire…» types;
- AL resistance within
0 to 1,5 kOhm
for
«fire
combined double-event
» type;
- AL resistance within
1,5 to 3,0 kOhm
for
«fire
combined single-event
» type
T
«
Alarm
» or «
Violation
» status for ALs of «intrusion»
and
«technological» types respectively.
AL resistance within
0 to 3,0 kOhm
or
5,0 kOhm to
open circuit
.
For HKP
2-nd item
PNC
SOS button is pressed
NOR
Normal state
3-rd item
ALM
AL2 (Zone 2) is in Violation status
NOR
AL2 (Zone 2) is in Normal status
For TTD 2-nd item
NSG
No signal with RTD