17
WARNING!
According to the requirements of regulatory framework the minimal delay time
before alerting start is 30 seconds. The delay is provided to cancel alerting in
case of false alarm.
When setting the delay time, please, take into account the additional time
required for data exchange between keypad and control panel while login, select
appropriate menu item, and transfer of the cancellation command. This time
averages about 15 seconds and must be taken into account when setting the
delay time.
7.3.3
The
«4.Failures»
menu item allows viewing existing failures with filters:
«1.By part. number»
- failures, service required and sabotages
«2.Sabotage»
- tampering and detachment from the installation
surface
«3.Failure»
- all critical failures except tampering and
detachment.
«4.Service required»
- non-critical failures that require service to devices,
but do not cause the
«not ready»
partition status
(for example: main BAT discharge).
When the
«1.By part. number»
filter is selected, information is displayed as described
in Paragraph
7.2.3
.
Selecting the
«2.Sabotage»
filter displays a list; paging through
the list using the ▼
and ▲ buttons sequentially switches to the following type of screens:
Using the
«3.Failure»
and
«4.Service req.»
filters results in displaying similar to the
«2.Sabotage»
filter.
Example
of screens:
or
Select
«5.All»
sub-item to view a list of all failures, which can be paged through using
the ▼ and ▲ buttons.
IP 0004
tamper
IP 0004
BPS low volt.
MC 0034
no comm.