5.4 FAULTS AND POSSIBLE REMEDIES
Anomalia
Causa
Rimedio
U/INS/CAT
The compressor
does not start
Power failure
Verify the presence of voltage
INS
main switch in pos. OFF
Check the upstream safety systems
U
low supply voltage
Check power line
INS
Fault compressor condenser
Replace the part
CAT
compressor failure
Replace the part
CAT
High pressure operation
Rearm pressostatato
U/INS/CAT
Yield
insufficien
Lack of coolant
Check
INS
Wrong size of the equipment
Check
INS
Operation outside of the conditions the
manufacturer’s recommended operating
Check
INS
Compressor
noisy
Part of the refrigerating circuit in contact with
the carpentry
Check
INS
Return of liquid to the compressor
Check charging / cleaning filter
CAT
not suitable unit fixin
Check
INS
Powered by reversed phase (400V models)
Reverse one phase
INS
Noise and
vibrations
Contact with metal bodies
Check and outdistance
IST
loose or missing screws
Tighten the screws
IST
The compressor
He stops for
intervention
protections
Excessive head pressure
Check
CAT
Low suction pressure
Check
CAT
low supply voltage
Check the power supply
INS
Electrical connections badly tightened
Check
INS
Operation outside the permissible limits
Check
INS
Bad operation or pressure probes
Replace the part
INS /CAT
Thermal protection trip
Check electrical insulation windings
CAT
Pressure
flo
High> 24 bar
Excessive refrigerant
Check
CAT
dirty filter fan units (in heat pump
Clean the filte
U/INS /CAT
Hot air layering (in heat pump)
Check
INS /CA
Pressing
aspiration
low <1 bar
Refrigerator discharge circuit
Check and reload
CAT
Exchanger evaporator side blocked
Check and if necessary replace the component
CAT
dirty filter fan units (cooling
Clean filte
U/INS /CAT
Absorption
high electrical
Refrigerant pressure is too high compared to
what is recommended
Check maximum absorption expected in data
and characteristics table
INS/CAT
Wrong pressure valve adjustment
Calibrated valve pressure switch
INS/CAT
Voltage does not comply
Check voltage supply
IST
The water of
cooling
It circulates also in
machine off
Pressure valve not calibrated properly
Calibrate the pressure valve
INS /CAT
The blower does
not work
off blower fan and
spies
extinguished
Power failure
Verify the presence of voltage
U/INS
main switch in pos. OFF
Check the upstream safety systems
U/INS
Intervention safety pressure AP
(high pressure)
Check the water flow and eset the pressure
switch by pressing the button behind the
black cap on the front panel (in case of dual
compressor model there are 2 buttons, press
them both)
U/INS/CAT
MAINTENANCE UNIT