21
Group10- PID function Setup
No. Description
Range
Factory
Setting
Note
10-00
PID target
value
selection
(when
00-05\00-06
=6
,this function
is enabled)
0: Potentiometer
on Keypad
1: Analog Signal
Input. (AVI)
2: Analog Signal
Input. (ACI)
3: Frequency set
by communication
4: KeyPad
Frequency
parameter 10-02
5: Preset
frequency
1 *1
10-01
PID
feedback
value
selection
0: Potentiometer
on Keypad
1: Analog Signal
Input. (AVI)
2: Analog Signal
Input. (ACI)
3: Communication
Setting Frequency
2 *1
10-02
PID Target
(keypad
input)
0.0~100.0 50.0
*1
10-03
PID Mode
Selection
0: Disabled
1: Deviation D
Control. FWD
Characteristic.
2: Feedback D
Control FWD
Characteristic.
3: Deviation D
Control Reverse
Characteristic.
4: Feedback D
Control Reverse
Characteristic.
5: Frequency
C
Deviation D
Control. FWD
Characteristic.
6: Frequency
C
Feedback D
Control FWD
Characteristic.
7: Frequency
C
Deviation D
Control Reverse
Characteristic.
8: Frequency
C
Feedback D
Control Reverse
Characteristic.
0
10-04
Feedback
Gain
Coefficient
0.00 ~ 10.00
1.00
*1
Group10- PID function Setup
No. Description
Range
Factory
Setting
Note
10-05
Proportional
Gain
0.0 ~ 10.0
3.0
*1
10-06
Integral
Time
0.0 ~ 100.0
0.5
*1
10-07
Derivative
Time
0.00 ~ 10.00
0.00
*1
10-08
PID Offset 0: Positive
1: Negative
0 *1
10-09
PID Offset
Adjust
0 ~ 109
0
*1
10-10
PID Output
Lag Filter
Time
0.0 ~ 2.5
0.0
*1
10-11
Feedback
Loss
Detection
Mode
0: Disabled
1: Drive keeps
running after
feedback loss
2: Drive stops after
feedback loss
0
10-12
Feedback
Loss
Detection
Level
0 ~ 100
0
10-13
Feedback
Loss
Detection
Delay Time
0.0 ~25.5
1.0
10-14
Integration
Limit Value
0 ~ 109
100
*1
10-15
Integral
Value
Resets to
Zero when
Feedback
Signal
Equals
the Target
Value
0: Disabled
1: 1 Second
30: 30 Seconds (0
~ 30)
0
10-16
Allowable
Integration
Error Margin
(units)(1unit
= 1/8192)
0 ~ 100
0
10-17
PID Sleep
Frequency
Level
0.00~599.00 0.00
10-18
PID Sleep
Function
Delay Time
0.0 ~25.5
0.0
10-19
PID Wake
up
frequency
Level
0.00 ~ 599.00
0.00
10-20
PID Wake
up function
Delay Time
0.0 ~ 25.5
0.0
10-21
Max PID
Feedback
Setting
0 ~999
100
*1
10-22
Min PID
0 ~999
0
*1
Содержание L510-101-SH1-N
Страница 1: ......
Страница 30: ...2 1 4 5 5 1 5 10 50 1 95 RH 1 10 50 10 40 1 6...
Страница 31: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 33: ...5 2 2 2 PNP 200V L510 2P2 SH1 F P L510 2P5 SH1 F P L510 201 SH1 F P L510 202 SH1 F P L510 203 SH1 F P...
Страница 35: ...7 2 2 4 PNP 400V L510 401 SH3 F P L510 402 SH3 F P L510 403 SH3 F P...
Страница 39: ...11 3 3 1 00 01 V F 02 03 04 05 06 07 08 09 10 PID 11 12 13 14 PUMP 1 v07 2 3 4...
Страница 63: ...L510s EMC EMC EMC 2P2 2P5 201 202 203...
Страница 64: ......