15
Group 03- Multi function Digital
Inputs/Outputs
No. Description
Range
Factory
Setting
Note
03-00
Multifunction
Input Term.
S1
0: Forward/Stop
Command or Run
/Stop
1: Reverse/Stop
Command Or
REV/FWD
2: Preset Speed
setting bit 0 (5-02)
3: Preset Speed
setting bit 1 (5-03)
4: Preset Speed
setting bit 2 (5-05)
6: Jog Forward
Command
7: Jog Reverse
Command
8: Up Command
9: Down Command
10: Acc/Dec 2
11: Acc/Dec
Disabled
12: Main
/
Alternative Run
Command select
13: Main
/
Alternative
Frequency
Command select
14: Rapid Stop
( Decel to stop)
15: Base Block
16: Disable PID
Function
17: Reset
18: Auto Run Mode
enable
19: Forced
Frequency
Run(pump model
only)
20: Switch to
Constant Pressure
2(pump
model
only)
0
03-01
Multifunction
Input Term.
S2
1
03-02
Multifunction
Input Term.
S3
2
03-03
Multifunction
Input Term.
S4
3
03-04
Multifunction
Input Term.
S5
17
03-05
Reserved
03-06
Up/Down
frequency
band
0.00~5.00
0.00
03-07
Up/Down
Frequency
modes
0: Preset
frequency is held
as the inverter
stops, and the
UP/Down function
is disabled.
0
1: Preset
frequency is reset
to 0 Hz as the
inverter stops.
Group 03- Multi function Digital
Inputs/Outputs
No. Description
Range
Factory
Setting
Note
2: Preset
frequency is held
as the inverter
stops, and the
UP/Down is
available.
03-08
S1~S5 scan
confirmation
1~200. Number
of Scan cycles
10
03-09
S1~ S5
switch type
select
xxxx0:S1 NO
xxxx1:S1 NC
00000
xxx0x:S2 NO
xxx1x:S2 NC
xx0xx:S3 NO
xx1xx:S3 NC
x0xxx:S4 NO
x1xxx:S4 NC
0xxxx:S5 NO
1xxxx:S5 NC
03-10
Reserved
03-11
Output
Relay(RY1)
0: Run
1
1: Fault
2: Setting
Frequency
Reached
3: Frequency
Reached
(3-13±3-14)
4: Output
Frequency
Detection1(> 3-13)
5: Output
Frequency
Detection2(< 3-13)
6: Auto-Restart
7: Momentary AC
Power Loss
8: Rapid Stop
9: Base Block
10: Motor Overload
Protection(OL1)
11: Drive Overload
Protection(OL2)
12: Reserved
13: Output Current
Reached
14: Brake Control
15: PID feedback
disconnection
detection
16: High Pressure
Detection
17: Low Pressure
Detection
18: Pressure Loss
Detection
03-13
Output
frequency
detection
0.00~599.00 0.00
*1
Содержание L510-101-SH1-N
Страница 1: ......
Страница 30: ...2 1 4 5 5 1 5 10 50 1 95 RH 1 10 50 10 40 1 6...
Страница 31: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 33: ...5 2 2 2 PNP 200V L510 2P2 SH1 F P L510 2P5 SH1 F P L510 201 SH1 F P L510 202 SH1 F P L510 203 SH1 F P...
Страница 35: ...7 2 2 4 PNP 400V L510 401 SH3 F P L510 402 SH3 F P L510 403 SH3 F P...
Страница 39: ...11 3 3 1 00 01 V F 02 03 04 05 06 07 08 09 10 PID 11 12 13 14 PUMP 1 v07 2 3 4...
Страница 63: ...L510s EMC EMC EMC 2P2 2P5 201 202 203...
Страница 64: ......