27
Display
Corrective action
Err2
1.modify11-08~11-10
or 11-11
2.00- 12>00-13
3.set 00-05 and 00-06 to
be different
4.set 03-21 <03-20
5.PTC function source can
not be set the same
source(AVI) with
frequency command
and PID command.
6.Please set correct
password
Err5
1.Issue enable command
before communication
2.Set parameters 09-02~
09-05 function before
communication
Err6
1.Check hardware and
wiring
2.Check Functions(09-00~
09- 05).
3.CON2 needs to connect
to the earth.
4.Please increase the
setting value of 09-08
Err7
If reset is not possible,
please consult with the
supplier.
4.1.3 Special conditions
Display
Description
StP0
In V/f mode, STP0 comes
out at less than 1.3Hz
(50Hz set) or at less than
1.5Hz (60Hz set)
In SLV mode, STP0
comes out at less than
1Hz
StP1
1. If the inverter is set for
external terminal control
mode (00-02/00-03=1) and
direct start is disabled
(07-04=1)
2. The inverter cannot be
started and will flash
STP1.
3. The run input is active at
power-up, refer to
descriptions of (07-04).
Display
Description
StP2
1. If the Stop key is
pressed while the inverter
is set to external control
mode (00-02/00-03=1)
then‘STP2’flashes after
stop.
2. Release and re-activate
the run contact to restart
the inverter.
E.S.
When external rapid stop
input is activated the
inverter will decelerate to
stop and the display will
flash with E.S. message.
b.b.
When external base
block input is activated
the inverter stops
immediately and then
the display will flash
with b.b. message.
PdEr
PID feedback loss is
detected.
Alter
other errors show up in the
process of auto tuning.
OH3
If 08-10 = 3, When over
temperature is detected by
signal at terminal AVI
increasing above the
warning detection limit set
in parameter 08-15, then
the display will show
“OH3”(motor
over heat warning level)
and the motor will continue
to run.
LOPB
Check if feedback value of
pressure is lower than limit
of minimum pressure
HIPB
Check if feedback value of
pressure is lower than limit
of maximum pressure.
COPUP
Communication breaking
or disconnection of pump
cascade control.
Содержание L510-101-SH1-N
Страница 1: ......
Страница 30: ...2 1 4 5 5 1 5 10 50 1 95 RH 1 10 50 10 40 1 6...
Страница 31: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 33: ...5 2 2 2 PNP 200V L510 2P2 SH1 F P L510 2P5 SH1 F P L510 201 SH1 F P L510 202 SH1 F P L510 203 SH1 F P...
Страница 35: ...7 2 2 4 PNP 400V L510 401 SH3 F P L510 402 SH3 F P L510 403 SH3 F P...
Страница 39: ...11 3 3 1 00 01 V F 02 03 04 05 06 07 08 09 10 PID 11 12 13 14 PUMP 1 v07 2 3 4...
Страница 63: ...L510s EMC EMC EMC 2P2 2P5 201 202 203...
Страница 64: ......