Group 14 PUMP Application Function
No. Description
Range
Factory
Setting
Note
Setting of
Pressure
Transmitter
14-04
Pump
Pressure
Command
Source
0
:
Set by 14-02
1
:
Set by AI
0
14-05
Display
Mode
Selection
0: Display of
Target and
Pressure
Feedback
(14-03<99)
1: Target Pressure
Only
2: Feedback
Pressure Only
0
14-06
Proportion
Gain(P)
0.00~10.00 3.00
14-07
Integral
Time(I)
0.0~100.0 0.5
14-08
Differential
Time(D)
0.00~10.00 0.00
14-09
Tolerance
Range of
Constant
Pressure
When 14-20=0,
range is
0.00~650.00
When 14-20=1,
range is 0~100
5
14-10
Sleep
Frequency
of Constant
Pressure
0.00~599.00 30.00
14-11
Sleep Time
of Constant
Pressure
0.0~255.5 0.0
14-12
Maximum
Pressure
Limit
When 14-20=0,
range is
0.00~650.00
When 14-20=1,
range is 0~100
50
14-13
Warning
Time of High
Pressure
0.0~600.0 10
14-14
Stop Time of
High
Pressure
0.0~600.0 20
14-15
Minimum
Pressure
Limit
When 14-20=0,
range is
0.00~650.00
When 14-20=1,
range is 0~100
5
14-16
Warning
Time of Low
Pressure
0.0~600.0 0.0
14-17
Fault Stop
Time of Low
Pressure
0.0~600.0 0.0
14-18
Time of Loss
Pressure
Detection
0.0~600.0 0.0
14-19
Proportion 0~100
0
Group 14 PUMP Application Function
No. Description
Range
Factory
Setting
Note
of Loss
Pressure
Detection
14-20
Switching of
Pressure
and
Percentage
0: Pressure
1: Percentage
1
14-22
Slave Trip
Frequency
0.00 ~ 599.00
45.00
14-23
Direction of
Water
Pressure
Detection
0: Upward
Detection
1: Downward
Detection
1
14-24
Range of
Water
Pressure
Detection
When 14-20=0,
range is
0.00~650.00
When 14-20=1,
range is 0~100
1
14-25
Period of
Water
Pressure
Detection
0.0~200.0 30.0
14-26
Acceleration
Time of
Water
Pressure
Detection
0.1~3600.0 12.0
14-27
Deceleration
Time of
Water
Pressure
Detection
0.1~3600.0 35.0
14-28
Forced Run
Command
0.00~(the value of
00-12)
0.00
14-29
Switching
Time of
Water
Pressure
Detection
0~240 3
14-30
Detection
Time of
Multiple
Pumps in
Parallel
Running
Start
0~30.0 0.0
14-31
Synchronou
s Selection
of Multiple
Pumps in
Parallel
0: Disable
1: Pressure Setting
Run/Stop
2: Pressure Setting
3: Run/Stop
1
14-34
Tolerance
Range of
Constant
Pressure 2
When 14-20=0,
range is
0.00~650.00
When 14-20=1,
range is 0~100
5
14-35
Selection of
Multiple
Pumps Shift
Operation
0: No Function
1: Timer
Alternately
Selection
1
Содержание L510-101-SH1-N
Страница 1: ......
Страница 30: ...2 1 4 5 5 1 5 10 50 1 95 RH 1 10 50 10 40 1 6...
Страница 31: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 33: ...5 2 2 2 PNP 200V L510 2P2 SH1 F P L510 2P5 SH1 F P L510 201 SH1 F P L510 202 SH1 F P L510 203 SH1 F P...
Страница 35: ...7 2 2 4 PNP 400V L510 401 SH3 F P L510 402 SH3 F P L510 403 SH3 F P...
Страница 39: ...11 3 3 1 00 01 V F 02 03 04 05 06 07 08 09 10 PID 11 12 13 14 PUMP 1 v07 2 3 4...
Страница 63: ...L510s EMC EMC EMC 2P2 2P5 201 202 203...
Страница 64: ......