19
Group 07- Start/Stop command setup
No. Description
Range
Factory
Setting
Note
Brake Start
Frequency
(Hz) In Stop
mode
07-07
DC Injection
Brake Level
(%) In stop
mode
0 ~ 20 (Frame1/2).
Based on the 20%
of maximum output
voltage 5
0 ~ 100 (Frame3/4)
based on the rated
current 50
07-08
DC Injection
Brake Time
(Seconds)
In stop
mode
0.0 ~ 25.5
0.5
07-09
Stopping
Method
0: Deceleration to
stop
1: Coast to stop
0
07-10
DC Braking
Level at
Start
0 ~ 20 (Frame1/2).
Based on the 20%
of maximum output
voltage
0
0 ~ 100 (Frame3/4)
based on the rated
current
50
07-11
DC Braking
Time at Start
0.0~25.5 0.0
07-12
Run
Command
Retention
0: Run command
retention during
power loss
1: Run command
not retained during
power loss
1
Note:
Set 14-00=0, 07-12 will be set to 1 automatically.
Set 14-00=1, 07-12 will be set to 0 automatically.
Group 08- Drive & Motor Protection
functions
No. Description
Range
Factory
Setting
Note
08-00
Trip
Prevention
Selection
xxxx0: Enable Trip
Prevention During
Acceleration
xxxx1: Disable Trip
Prevention During
Acceleration
xxx0x: Enable Trip
Prevention During
Deceleration
xxx1x: Disable Trip
Prevention During
Deceleration
xx0xx: Enable Trip
Prevention in Run
Mode
xx1xx: Disable Trip
00000
Group 08- Drive & Motor Protection
functions
No. Description
Range
Factory
Setting
Note
Prevention in Run
Mode
x0xxx: Enable over
voltage Prevention
in Run Mode
x1xxx: Disable
over voltage
Prevention
in Run Mode
08-01
Trip
Prevention
Level
During
Acceleration
(%)
50 ~ 200
by series
08-02
Trip
Prevention
Level
During
Deceleration
(%)
50 ~ 200
by series
08-03
Trip
Prevention
Level In
Run Mode
(%)
50 ~ 200
by series
08-04
over voltage
Prevention
Level in Run
Mode
200V: 350.0~390.0
400V: 700.0~780.0
380.0/76
0.0
*1
08-05
Electronic
Motor
Overload
Protection
Operation
Mode
xxxx0: Disable
Electronic Motor
Overload
Protection
00001
xxxx1: Enable
Electronic Motor
Overload
Protection
xxx0x: Motor
Overload Cold
Start
xxx1x: Motor
Overload Hot Start
xx0xx: Standard
Motor
xx1xx: Invertor
Duty Motor ( Force
Vent)
08-06
Operation
After
Overload
Protection is
Activated
0: Coast-to-Stop
After Overload
Protection is
Activated
1: Drive Will Not
Trip when
Overload
Protection is
Activated (OL1)
0
Содержание L510-101-SH1-N
Страница 1: ......
Страница 30: ...2 1 4 5 5 1 5 10 50 1 95 RH 1 10 50 10 40 1 6...
Страница 31: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 33: ...5 2 2 2 PNP 200V L510 2P2 SH1 F P L510 2P5 SH1 F P L510 201 SH1 F P L510 202 SH1 F P L510 203 SH1 F P...
Страница 35: ...7 2 2 4 PNP 400V L510 401 SH3 F P L510 402 SH3 F P L510 403 SH3 F P...
Страница 39: ...11 3 3 1 00 01 V F 02 03 04 05 06 07 08 09 10 PID 11 12 13 14 PUMP 1 v07 2 3 4...
Страница 63: ...L510s EMC EMC EMC 2P2 2P5 201 202 203...
Страница 64: ......