Group 08 Protection Parameters
08- 00
Stall prevention function
Range
【xxx0b】:
Stall prevention function is enabled during acceleration.
【xxx1b】:
Stall prevention function is disabled during acceleration.
【xx0xb】:
Stall prevention function is enabled during deceleration.
【
xx1xb】:
Stall prevention function is disabled during deceleration.
【x0xxb】:
Stall prevention function is enabled during operation.
【
x1xxb】:
Stall prevention function is disabled during run.
【0xxxb】:
Stall prevention function during run is based on the first
acceleration time.
【
1xxxb】:
Stall prevention function during run is based on the second
acceleration time.
08- 01
Stall prevention level during acceleration
Range
【
20~200
】%
08- 02
Stall prevention level during deceleration
Range
200V :【330V~410V】
400V :【660V~820V】
08- 03
Stall prevention level during run
Range
【
30~200
】%
08-21
Limit of stall prevention during acceleration
Range
【
1~100
】%
08-22
Stall prevention detection time during run
Range
【
2~100
】mSec
08- 40
Motor 2 Acceleration Stall Prevention Level
Range
【
20~200
】%
08-41
Motor 2 Acceleration Stall Prevention Limit
Range
【
1~100
】%
Note:Stall prevention function only can be set in V/F control mode.
Stall prevention during acceleration (08-00=xxx0b)
(1)
Prevents the inverter from faulting (Overcurrent, Motor overload, Inverter overload) when
accelerating with heavy loads.
(2)
When the inverter output current reaches the level set in parameter 08-01 minus 15% the
acceleration rate starts to decrease. When the inverter output current reaches the level set in
parameter 08-01 the motor stops accelerating.
(3)
Reduce stall prevention level during acceleration (08-01) in case the motor stalls (when the
motor power is smaller than the inverter rating.
Содержание E510-201-SH
Страница 1: ......
Страница 20: ...3 6 NEMA1 Step1 Remove the terminal cover Step2 Wire Re install the cover Step3 Put the terminal cover back ...
Страница 27: ...3 13 3 2 3 External View 3 2 3 1 IP20 NEMA 1 a 200V 0 5HP 1HP 400V 1HP 2HP 200V 2HP 3PH IP20 NEMA1 ...
Страница 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Страница 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Страница 47: ...3 33 Frame2 Three phase 200V 3HP Frane 5 6 Three 200V 25HP Frame 5 6 Three phase 200V 30HP 40HP ...
Страница 49: ...3 35 Frame 5 Three phase 400V 30HP Frame 6 Three phase 400V 40HP 50HP Frame 6 Three phase 400V 60HP 75HP ...
Страница 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Страница 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Страница 74: ...4 8 4 1 5 Operation control ...
Страница 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Страница 310: ...4 244 P mode output i1 PQ1 I1 OFF ON OFF ON OFF ON OFF i1 is the inverse logic of I1 i1 Q1 ON OFF ON OFF ...
Страница 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Страница 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Страница 425: ......