4-237
Fig. 4.3.109 Dual pumps start up process
A.
Dual pumps are enabled during this time. Master starts up first and Slave is in standby to enter
constant-pressure operation.
B.
Large water consumption results in the higher operation frequency of Master. If water pressure
is not lower than the tolerance range of constant-pressure and the operation time is not over
the detection time (23-30), Slave is still in standby.
C.
If it is over the detection time (23-30), and Master runs at 60Hz, Master informs Slave of
auxiliary kicking water. After Slave operates, the operation frequency of Master and Slave
reduces to the operation of constant-pressure if water consumption is stable.
D.
If water consumption is mild, the operation frequency of Master and Slave reduces. Because the
water consumption is less than that of the operation of dual pumps, Slave stops to sleep
(please refer to parameter 23-22 for dual pump slave sleep requirements) and only Master runs
to reach constant-pressure operation.
Note 1:
When 23-35=3, If the operation time is over the switching time (23-29) or sleep to stop under the
operation of dual pumps, the dominance between Master and Slave will exchange to operate.
Note 2:
When 23-01≠0, the parameter 23-01 of these two inverters can not be simultaneously set to 1 or 2.
That is, the parameter 23-01 of one inverter is set to 1 and that of the other inverter should be set to
2 and vice versa.
Содержание E510-201-SH
Страница 1: ......
Страница 20: ...3 6 NEMA1 Step1 Remove the terminal cover Step2 Wire Re install the cover Step3 Put the terminal cover back ...
Страница 27: ...3 13 3 2 3 External View 3 2 3 1 IP20 NEMA 1 a 200V 0 5HP 1HP 400V 1HP 2HP 200V 2HP 3PH IP20 NEMA1 ...
Страница 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Страница 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Страница 47: ...3 33 Frame2 Three phase 200V 3HP Frane 5 6 Three 200V 25HP Frame 5 6 Three phase 200V 30HP 40HP ...
Страница 49: ...3 35 Frame 5 Three phase 400V 30HP Frame 6 Three phase 400V 40HP 50HP Frame 6 Three phase 400V 60HP 75HP ...
Страница 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Страница 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Страница 74: ...4 8 4 1 5 Operation control ...
Страница 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Страница 310: ...4 244 P mode output i1 PQ1 I1 OFF ON OFF ON OFF ON OFF i1 is the inverse logic of I1 i1 Q1 ON OFF ON OFF ...
Страница 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Страница 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Страница 425: ......