Group 07 Start/Stop Parameters
07- 00
Momentary power loss and restart
Range
【0】:Disable
【1】:Enable
07- 01
Fault reset time
Range
【0~7200】 Sec
07- 02
Number of restart attempts
Range
【0~10】
07- 03
Reset Mode Setting
Range
【0】:Enable Reset Only when Run Command is Off
【1】:Enable Reset when Run Command is On or Off
When 07-00=1, If the input power supply due to sudden increase in supply demand by
other equipment results in voltage drops below the under voltage level, the inverter will
stop its output at once.
07-00=0:When power loss exceed 2ms,
“
UV fault
”
will be detected.
07-00=1:Aafter a momentary power loss, inverter will restart with half frequency
before power loss, and there is no limitation on number of restarts.
The automatic restart function is active for the following faults. Please note that when the fault is not
listed in the table the inverter will not attempt an automatic restart.
Parameter
Faults
Number of Restart
07-00
UV
(Under Voltage)
Unlimited
07-01
07-02
OC: Over current
Depend on parameter 07-02
OCA: Over current in acceleration
OCC: Over current in constant speed
OCd: Over current in deceleration
OL1: motor overload
UT: Under torque detection
IPL: Input phase loss
GF: Ground failure
OV: Overvoltage
OL2: Inverter overload
OT: Over-torque detection
OPL: Output phase loss
CF07: SLV motor control setting fault
CF08: PMSLV motor control setting fault
Notes
:
(1)
Fault restart function contains momentary power loss restart and auto reset restart.
(2)
Refer to chapter 10 for the details of troubleshooting and fault diagnostics.
(3)
Refer to speed search function (07-19~07-24) for the selection of speed search modes.
Содержание E510-201-SH
Страница 1: ......
Страница 20: ...3 6 NEMA1 Step1 Remove the terminal cover Step2 Wire Re install the cover Step3 Put the terminal cover back ...
Страница 27: ...3 13 3 2 3 External View 3 2 3 1 IP20 NEMA 1 a 200V 0 5HP 1HP 400V 1HP 2HP 200V 2HP 3PH IP20 NEMA1 ...
Страница 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Страница 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Страница 47: ...3 33 Frame2 Three phase 200V 3HP Frane 5 6 Three 200V 25HP Frame 5 6 Three phase 200V 30HP 40HP ...
Страница 49: ...3 35 Frame 5 Three phase 400V 30HP Frame 6 Three phase 400V 40HP 50HP Frame 6 Three phase 400V 60HP 75HP ...
Страница 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Страница 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Страница 74: ...4 8 4 1 5 Operation control ...
Страница 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Страница 310: ...4 244 P mode output i1 PQ1 I1 OFF ON OFF ON OFF ON OFF i1 is the inverse logic of I1 i1 Q1 ON OFF ON OFF ...
Страница 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Страница 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Страница 425: ......