4-129
03-24
Output Under Current Detection
Range
【0】:Invalid
【1】:Valid
03-25
Output Under Current Detection Level
Range
【0~999.9】A
03-26
Output Under Current Detection Delay Time
Range
【0.0~655.34】 Sec
If 03-11=55, when output current
≦
03-25, output relay is active.
When 03-25=0, the function will be disabled.
When output current lower than 03-25 for a preset time (03-26), output relay is active. The
delay time of output relay from ON to OFF is 100ms (constant).
The timing chart:
03-26
Fixed
100msec
03-25
03-11
Relay
ON
I (Loading current)
100%
T
Operation
Command
ON
Smaller than 03-26
Relay does not work
Содержание E510-201-SH
Страница 1: ......
Страница 20: ...3 6 NEMA1 Step1 Remove the terminal cover Step2 Wire Re install the cover Step3 Put the terminal cover back ...
Страница 27: ...3 13 3 2 3 External View 3 2 3 1 IP20 NEMA 1 a 200V 0 5HP 1HP 400V 1HP 2HP 200V 2HP 3PH IP20 NEMA1 ...
Страница 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Страница 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Страница 47: ...3 33 Frame2 Three phase 200V 3HP Frane 5 6 Three 200V 25HP Frame 5 6 Three phase 200V 30HP 40HP ...
Страница 49: ...3 35 Frame 5 Three phase 400V 30HP Frame 6 Three phase 400V 40HP 50HP Frame 6 Three phase 400V 60HP 75HP ...
Страница 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Страница 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Страница 74: ...4 8 4 1 5 Operation control ...
Страница 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Страница 310: ...4 244 P mode output i1 PQ1 I1 OFF ON OFF ON OFF ON OFF i1 is the inverse logic of I1 i1 Q1 ON OFF ON OFF ...
Страница 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Страница 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Страница 425: ......