background image

 

 
 

 

 
Cod.Doc.2550041-REV 2.2.0 gb.doc  

Pagina 4 

 

 
-  This electric panel has only to be used for the purpose for which it was specifically designed. Any other use shall be considered improper and, 

therefore, dangerous. 

-  Our products are made in conformity with current safety standards so it is recommended to use all these devices and take care that their use causes 

no injury or damage. 

-  All operations concerning the installation of the control panel should be carried out by skilled personnel in conformity with present regulations.  

-  During work it is recommended to keep to the current personal safety rules in force in the country the product is destined for (clothing, work tools, 

etc.). 

-  When the unit is working do not use the electric control board parts. 

-  Never for any reason modify any part of the electric panel (connections, holes, electrical or mechanical devices, etc.) unless duly authorized to do so 

in writing by “

TECNOELETTRA

”: the responsibility deriving from any such action shall fall on the person doing it since he then in fact becomes its 

manufacturer.  

-  Before doing any cleaning or maintenance, 

de-energise

 and switch off the machine it is connected to. 

De-energise and disconnect the equipment in the event of breakdown or malfuncion. If any repairs is needed contact an 

Authorized Retailer only 

and ask that only original spare parts are used

. Failing to observe the above instructions may put the safety of the electric control board at risk  

and the warranty will immediately decline. 

When installing the control panel comply with the IP protection seal indicated on the identification plate. If the IP protection seal is not indicated and 
for different kinds of "IP" protections diverse contact one of our service centres or contact our technical office directly. 

 
-  Make sure that earthing complies with the standards in force in the country in which the appliance is used. 

-  Check that control panels that are installed on the machine are not subjected to vibrations that could damage the parts.  

N.B.: The panel size depends on an ambient temperature of 35 degrees Centigrade. 
-  As a consequence, please make sure that these levels are complied with. As concerns atmospheric conditions, the prescriptions contained in the CEI 

EN 60439-1 (6.1.2) have to be complied with. 

-  Check that the information on the control panel identification plate is compatible with appliance ratings such as voltage, current, frequency, etc.  

-  If the control panel can be locked, make sure that only authorised personnel can use the key to open the control panel.  

-  For the protection of inlet lines are not protected comply strictly with the regulations in force in the country in which the control panel is used.  

-  If the control panel is fitted with guards that need to be removed to wire up the control panel, make sure that they are refitted after the control panel 

has been wired up. Make sure that the control panel is disconnected and locked out during these operations and that no parts carry residual current.  

-  Strictly follow the wiring diagram that accompanies the control panel. 

-  The manufacturer declines any responsability in to following cases: 

a

) misure of the machine or use by persons not trained for its operation. 

b

) incorrect installation. 

c

)  operating faults machine is applied who to electric control board. 

d

) serious lack of due maintenance. 

e

) unauthorized modifications or servicing. 

f

) use of non-original or non-specific spare parts for the model. 

g

) total or pairtial failure to follow the instruction. 

h) unforoseen events ect. 

 
The instruction manual can never substitute a sufficiently experienced user. 
 

 
The panels’ interruption power is 10 kA. For more powerful systems, please make sure that the right protection levels in the panel inlet lines are 
supplied. 

 
 Warning

: This booklet is not binding. “

TECNOELETTRA

” reserves the right, without prejudice to the essential features of the model herein 

described and illustrated, to make improvements and modifications to parts and accessories without moreover undertaking to update this 

manual in time. 

 
 
 

1.3 - Symbols in the manual 

 
The symbols contained in this manual have the purpose of drawing the user’s attention in order to prevent trouble or danger both for persons and 
objects or the equipment.  
 
These symbols moreover have the purpose of drawing your attention in order to indicate correct use and obtain good operation from your electric panel.  

Содержание AT206

Страница 1: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 1 ELECTRICAL PANEL AT206 AT206B USER MANUAL ...

Страница 2: ...ption 9 3 1 Operation to do during the first starting of the AT206 panel 9 3 1 1 How programming the time on the panel 9 3 2 AT206 panel LED indication decription 10 3 3 AT206 panel command buttons decription 10 3 4 AT206 panel function description 11 3 4 1 Procedure to setting tha automatic test 11 4 AT206 connection and electrical drawings 12 4 1 Power connection 12 4 1 1 Triphase connection 400...

Страница 3: ... initial performance and safety required by current standards are restored Use of non genuine spare parts shall immediately forfeit all right to warranty and Technical Service by TECNOELETTRA The special composition and design of this panel enables satisfying the most restrictive operator safety standards To use TECNOELETTRA Electric Panels in the best way below we give the most important rules to...

Страница 4: ...equence please make sure that these levels are complied with As concerns atmospheric conditions the prescriptions contained in the CEI EN 60439 1 6 1 2 have to be complied with Check that the information on the control panel identification plate is compatible with appliance ratings such as voltage current frequency etc If the control panel can be locked make sure that only authorised personnel can...

Страница 5: ...on is given by the flow of energy passing through the control components and by the management of the electric control panel 1 7 Cautions levels Below we give the symbols used in the manual to draw the reader s attention to the different levels of danger in the Use and Maintenance of the electric panel DANGER Information or procedures that unless carried out meticulously cause death or serious inj...

Страница 6: ... country it is destined for CAUTION In addition it is wise to destroy the machine s identification plate and any other documents 1 12 Assistance center All maintenance work and technical service must be performed by Specialized personnel authorized by TECNOELETTRA who will arrange for a technician to step in after the customer s call 1 13 Repairs and spare parts For any further inconveniences not ...

Страница 7: ...e The technical plate is secured on the outside of the electric panel it gives the main particulars and certifies its conformity with the EEC machine directive 89 392 attachment H Therefore its CE marking is valid only when mounted with machines made in accordance with the provisions of the EEC machine directive 89 392 and subsequent amendments introduced 91 368 EEC 83 44 EEC 93 68 EEC Every time ...

Страница 8: ...N IN EMERGENCY SITUATION PRESS THIS BUTTON TO STOP IMMEDIATLY THE GENERATOR Control board Predisposition for magnetothermic switch or earth failure relay IMP switch to supply 230Vac for auxiliary output OPTIONAL Buzzer B for acoustic alarm Input for generator power connection Input for mains power connection Output for load power connection Auxiliary connector CN1 Auxiliary connector CN2 F1 F4A F2...

Страница 9: ... display shows the first code of the parameter U 01 Automatic test interval time To see all the parameters please check the following table By continously pressing of MEAS button reach parameter U 11 showed on the display This parameter is about the actual time Press TEST button to see the value stored now Press START button to increase the value of the hour or press STOP button to increase the va...

Страница 10: ...he board is in AUTOMATIC Par 3 4 If on it indicates that the board is in RESET Par 3 4 It permit to activate the automatic test Par 3 4 Board in MANUAL function Par 3 4 It permit to change the type of measurement showed by the display It permit to close the mains contactor active only in MANUAL function press it with MAN button in the same time It permit to close the generator contactor active onl...

Страница 11: ...P button to decrease it When the value is correct press RESET button to save the modification and press AUT to exit from parameter This parameter specifies the delay from one automatic test and the next one If you don t press RESET before exit by pressing AUT modifications made on the parameter won t be saved By pressing MEAS button go to parameter U 02 showed on the display Press TEST button to s...

Страница 12: ... T3 T4 Load connection X0 Terminals sequence U V W N Generator phase 1 T1 Generator phase 2 T2 Generator phase 3 T3 Generator neutral T4 Common earth connection Genarator Mains Load Mains phase 1 T1 Mains phase 2 T2 Mains phase 3 T3 Mains neutral T4 Phase 1 load U It pass through TA before connection to load terminal U Phase 2 load V Phase 3 load W Neutral load N Amperemetric Transformer TA WARNIN...

Страница 13: ...T2 Generator phase 3 T3 Generator neutral T4 Common earth connection Genarator Mains Load Mains phase 1 T1 Mains phase 2 T2 Mains phase 3 T3 Mains neutral T4 Phase 1 load U It pass through TA before connection to load terminal U Phase 2 load V Phase 3 load W Neutral load N Amperemetric Transformer TA Warning Move blue wire n 14 from terminal T4 to terminal T3 Warning Move blue wire n 24 from termi...

Страница 14: ...poles T3 and T4 must be connected togheter T3 T4 Neutral By this connection the max current of the contactor is Ith x 1 6 Generator phase to use maximum contactor power poles T1 and T2 must be connected togheter T1 T2 phase By this connection the max current of the contactor is Ith x 1 6 Mains phase to use maximum contactor power poles T1 and T2 must be connected togheter T1 T2 phase By this conne...

Страница 15: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 15 4 2 AT206 panel electrical drawing ...

Страница 16: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 16 4 3 AT206B panel electrical drawing ...

Страница 17: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 17 4 4 Diesel engine auxiliary connection ...

Страница 18: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 18 4 5 Gasoline engine auxiliary connection ...

Страница 19: ...ntrance in the menu is showed by the display with the first code of the parameter U 01 This procedure permit to enter only in the User menu that permits to modify only the normal use parameters descripted in par 5 3 by this you are not able to enter in the technical parameters that can cause function problem in the panel these parameters are descripted in par 5 4 To have access to complete menu ad...

Страница 20: ... 01 Stop times electromagnet closing time gasoline engine stop time 1 30sec 10 02 Decelerated funct time 1 60 sec 30 03 Cooling time 1 300sec 120 Group 4 Protections P4 01 Minimum frequency fixed delay 5sec 80 100 90 02 Maximum frequency overspeed 100 120 110 03 Maximum frequency al tripping delay 0 15 sec 2 sec 04 Battery minimum frequency 7 12V 9 05 Battery maximum frequency 13 17V 17V 06 Load m...

Страница 21: ... 0001 0001 yes A2 05 Not used 0000 0001 0000 no A3 Avaria meccanica 0000 0001 0001 yes A3 01 Stop without cooling 0000 0001 0001 yes A3 02 Stop with cooling 0000 0001 0000 no A3 03 Siren relay 0000 0001 0001 yes A3 04 Alarm relay if enabled 0000 0001 0001 yes A3 05 Not used 0000 0001 0000 no A4 500 rpm failure strap breaking 0000 0001 0001 yes A4 01 Stop without cooling 0000 0001 0000 no A4 02 Sto...

Страница 22: ...Battery maximum voltage 0000 0001 0001 yes A12 01 Stop without cooling 0000 0001 0000 no A12 02 Stop with cooling 0000 0001 0001 yes A12 03 Siren relay 0000 0001 0001 yes A12 04 Alarm relay if enabled 0000 0001 0001 yes A12 05 Not used 0000 0001 0000 no A13 Starting failure 0000 0001 0001 yes A13 01 Stop without cooling not influential always as set to no 0000 0001 0000 no A13 02 Stop with cooling...

Страница 23: ...egularly stipulated in the contract PACKING It is always gratis WARRANTY AND GUARANTEE The Seller guarantees that the products the subject of the contract shall be free from defects including components and manufacture and specifications of the contract The warranty period is 12 months from the date the goods the subject of the contract are despatched from the Seller s premises The warranty is app...

Страница 24: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 24 ...