background image

 

 
 

 

 
Cod.Doc.2550041-REV 2.2.0 gb.doc  

Pagina 21 

 

 

Group 7 

Network parameters 

 

 

P7.01 

Mains voltage minimum threshold (measured) 

160 – 230Vac 

195Vac 

    .02 

Mains voltage maximum threshold (measured) 

200 – 345Vac 

260Vac 

    .03 

Mains voltage time out of the limits 

5 – 9999 sec 

5 sec 

    .04 

Mains voltage return time within the limits 

5 – 9999 sec 

10 sec 

 

 

 

 

 

 

 

 

 

 

 

 

Group 8 

Generator parameters 

 

 

P8.01 

Generator voltage minimum threshold (measured) 

160 – 230Vac 

195Vac 

    .02 

Generator voltage maximum threshold (measured) 

200 – 345Vac 

260Vac 

    .03 

Generator voltage delay out of the limits 

5 – 9999 sec              

5 sec 

    .04 

Generator voltage time within the limits 

5 – 9999 sec 

20 sec 

 

 

 

 

 

 

Alarms  

 

 

 

 

 

Setup Description 

Range 

Default 

 

 

    0000=no    0001=yes 

 

 

 

 

 

A1 

Engine overtemperature  

0000 / 0001 

0001 = yes 

A1.01 

Stop without cooling 

0000 / 0001 

0001 = yes 

A1.02 

Stop with cooling 

0000 / 0001 

0000 = no 

A1.03 Siren 

relay 

0000 / 0001 

0001 = yes 

A1.04 

Alarm relay (if enabled see P6.02) 

0000 / 0001 

0001 = yes 

A1.05 Not 

used 

0000 / 0001 

0000 = no 

 

 

 

 

A2 

Oil low pressure 

0000 / 0001 

0001 = yes 

A2.01 

Stop without cooling 

0000 / 0001 

0001 = yes 

A2.02 

Stop with cooling 

0000 / 0001 

0000 = no 

A2.03 Siren 

relay 

0000 / 0001 

0001 = yes 

A2.04 

Alarm relay (if enabled) 

0000 / 0001 

0001 = yes 

A2.05 Not 

used 

0000 / 0001 

0000 = no 

 

 

 

 

A3 

Avaria meccanica 

0000 / 0001 

0001 = yes 

A3.01 

Stop without cooling  

0000 / 0001 

0001 = yes 

A3.02 

Stop with cooling 

0000 / 0001 

0000 = no 

A3.03 Siren 

relay 

0000 / 0001 

0001 = yes 

A3.04 

Alarm relay (if enabled) 

0000 / 0001 

0001 = yes 

A3.05 Not 

used 

0000 / 0001 

0000 = no 

 

 

 

 

A4 

500 rpm failure (strap breaking) 

0000 / 0001 

0001 = yes 

A4.01 

Stop without cooling  

0000 / 0001 

0000 = no 

A4.02 

Stop with cooling 

0000 / 0001 

0000 = no 

A4.03 Siren 

relay 

0000 / 0001 

0001 = yes 

A4.04 

Alarm relay (if enabled) 

0000 / 0001 

0001 = yes 

A4.05 Not 

used 

0000 / 0001 

0000 = no 

 

 

 

 

A5 

Overspeed (maximum frequency) 

0000 / 0001 

0001 = yes 

A5.01 

Stop without cooling  

0000 / 0001 

0001 = yes 

A5.02 

Stop with cooling 

0000 / 0001 

0000 = no 

A5.03 Siren 

relay 

0000 / 0001 

0001 = yes 

A5.04 

Alarm relay (if enabled) 

0000 / 0001 

0001 = yes 

A5.05 Not 

used 

0000 / 0001 

0000 = no 

 

 

 

 

A6 

Minimum frequency (fixed delay 5sec) 

0000 / 0001 

0001 = yes 

A6.01 

Stop without cooling  

0000 / 0001 

0000 = no 

A6.02 

Stop with cooling 

0000 / 0001 

0001 = yes 

A6.03 Siren 

relay 

0000 / 0001 

0001 = yes 

A6.04 

Alarm relay (if enabled) 

0000 / 0001 

0001 = yes 

A6.05 Not 

used 

0000 / 0001 

0000 = no 

 

 

 

 

A7 

Generator minimum voltage 

0000 / 0001 

0001 = yes 

A7.01 

Stop without cooling 

0000 / 0001 

0001 = yes 

A7.02 

Stop with cooling 

0000 / 0001 

0000 = no 

A7.03 Siren 

relay 

0000 / 0001 

0001 = yes 

A7.04 

Alarm relay (if enabled) 

0000 / 0001 

0001 = yes 

A7.05 Not 

used 

0000 / 0001 

0000 = no 

Содержание AT206

Страница 1: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 1 ELECTRICAL PANEL AT206 AT206B USER MANUAL ...

Страница 2: ...ption 9 3 1 Operation to do during the first starting of the AT206 panel 9 3 1 1 How programming the time on the panel 9 3 2 AT206 panel LED indication decription 10 3 3 AT206 panel command buttons decription 10 3 4 AT206 panel function description 11 3 4 1 Procedure to setting tha automatic test 11 4 AT206 connection and electrical drawings 12 4 1 Power connection 12 4 1 1 Triphase connection 400...

Страница 3: ... initial performance and safety required by current standards are restored Use of non genuine spare parts shall immediately forfeit all right to warranty and Technical Service by TECNOELETTRA The special composition and design of this panel enables satisfying the most restrictive operator safety standards To use TECNOELETTRA Electric Panels in the best way below we give the most important rules to...

Страница 4: ...equence please make sure that these levels are complied with As concerns atmospheric conditions the prescriptions contained in the CEI EN 60439 1 6 1 2 have to be complied with Check that the information on the control panel identification plate is compatible with appliance ratings such as voltage current frequency etc If the control panel can be locked make sure that only authorised personnel can...

Страница 5: ...on is given by the flow of energy passing through the control components and by the management of the electric control panel 1 7 Cautions levels Below we give the symbols used in the manual to draw the reader s attention to the different levels of danger in the Use and Maintenance of the electric panel DANGER Information or procedures that unless carried out meticulously cause death or serious inj...

Страница 6: ... country it is destined for CAUTION In addition it is wise to destroy the machine s identification plate and any other documents 1 12 Assistance center All maintenance work and technical service must be performed by Specialized personnel authorized by TECNOELETTRA who will arrange for a technician to step in after the customer s call 1 13 Repairs and spare parts For any further inconveniences not ...

Страница 7: ...e The technical plate is secured on the outside of the electric panel it gives the main particulars and certifies its conformity with the EEC machine directive 89 392 attachment H Therefore its CE marking is valid only when mounted with machines made in accordance with the provisions of the EEC machine directive 89 392 and subsequent amendments introduced 91 368 EEC 83 44 EEC 93 68 EEC Every time ...

Страница 8: ...N IN EMERGENCY SITUATION PRESS THIS BUTTON TO STOP IMMEDIATLY THE GENERATOR Control board Predisposition for magnetothermic switch or earth failure relay IMP switch to supply 230Vac for auxiliary output OPTIONAL Buzzer B for acoustic alarm Input for generator power connection Input for mains power connection Output for load power connection Auxiliary connector CN1 Auxiliary connector CN2 F1 F4A F2...

Страница 9: ... display shows the first code of the parameter U 01 Automatic test interval time To see all the parameters please check the following table By continously pressing of MEAS button reach parameter U 11 showed on the display This parameter is about the actual time Press TEST button to see the value stored now Press START button to increase the value of the hour or press STOP button to increase the va...

Страница 10: ...he board is in AUTOMATIC Par 3 4 If on it indicates that the board is in RESET Par 3 4 It permit to activate the automatic test Par 3 4 Board in MANUAL function Par 3 4 It permit to change the type of measurement showed by the display It permit to close the mains contactor active only in MANUAL function press it with MAN button in the same time It permit to close the generator contactor active onl...

Страница 11: ...P button to decrease it When the value is correct press RESET button to save the modification and press AUT to exit from parameter This parameter specifies the delay from one automatic test and the next one If you don t press RESET before exit by pressing AUT modifications made on the parameter won t be saved By pressing MEAS button go to parameter U 02 showed on the display Press TEST button to s...

Страница 12: ... T3 T4 Load connection X0 Terminals sequence U V W N Generator phase 1 T1 Generator phase 2 T2 Generator phase 3 T3 Generator neutral T4 Common earth connection Genarator Mains Load Mains phase 1 T1 Mains phase 2 T2 Mains phase 3 T3 Mains neutral T4 Phase 1 load U It pass through TA before connection to load terminal U Phase 2 load V Phase 3 load W Neutral load N Amperemetric Transformer TA WARNIN...

Страница 13: ...T2 Generator phase 3 T3 Generator neutral T4 Common earth connection Genarator Mains Load Mains phase 1 T1 Mains phase 2 T2 Mains phase 3 T3 Mains neutral T4 Phase 1 load U It pass through TA before connection to load terminal U Phase 2 load V Phase 3 load W Neutral load N Amperemetric Transformer TA Warning Move blue wire n 14 from terminal T4 to terminal T3 Warning Move blue wire n 24 from termi...

Страница 14: ...poles T3 and T4 must be connected togheter T3 T4 Neutral By this connection the max current of the contactor is Ith x 1 6 Generator phase to use maximum contactor power poles T1 and T2 must be connected togheter T1 T2 phase By this connection the max current of the contactor is Ith x 1 6 Mains phase to use maximum contactor power poles T1 and T2 must be connected togheter T1 T2 phase By this conne...

Страница 15: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 15 4 2 AT206 panel electrical drawing ...

Страница 16: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 16 4 3 AT206B panel electrical drawing ...

Страница 17: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 17 4 4 Diesel engine auxiliary connection ...

Страница 18: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 18 4 5 Gasoline engine auxiliary connection ...

Страница 19: ...ntrance in the menu is showed by the display with the first code of the parameter U 01 This procedure permit to enter only in the User menu that permits to modify only the normal use parameters descripted in par 5 3 by this you are not able to enter in the technical parameters that can cause function problem in the panel these parameters are descripted in par 5 4 To have access to complete menu ad...

Страница 20: ... 01 Stop times electromagnet closing time gasoline engine stop time 1 30sec 10 02 Decelerated funct time 1 60 sec 30 03 Cooling time 1 300sec 120 Group 4 Protections P4 01 Minimum frequency fixed delay 5sec 80 100 90 02 Maximum frequency overspeed 100 120 110 03 Maximum frequency al tripping delay 0 15 sec 2 sec 04 Battery minimum frequency 7 12V 9 05 Battery maximum frequency 13 17V 17V 06 Load m...

Страница 21: ... 0001 0001 yes A2 05 Not used 0000 0001 0000 no A3 Avaria meccanica 0000 0001 0001 yes A3 01 Stop without cooling 0000 0001 0001 yes A3 02 Stop with cooling 0000 0001 0000 no A3 03 Siren relay 0000 0001 0001 yes A3 04 Alarm relay if enabled 0000 0001 0001 yes A3 05 Not used 0000 0001 0000 no A4 500 rpm failure strap breaking 0000 0001 0001 yes A4 01 Stop without cooling 0000 0001 0000 no A4 02 Sto...

Страница 22: ...Battery maximum voltage 0000 0001 0001 yes A12 01 Stop without cooling 0000 0001 0000 no A12 02 Stop with cooling 0000 0001 0001 yes A12 03 Siren relay 0000 0001 0001 yes A12 04 Alarm relay if enabled 0000 0001 0001 yes A12 05 Not used 0000 0001 0000 no A13 Starting failure 0000 0001 0001 yes A13 01 Stop without cooling not influential always as set to no 0000 0001 0000 no A13 02 Stop with cooling...

Страница 23: ...egularly stipulated in the contract PACKING It is always gratis WARRANTY AND GUARANTEE The Seller guarantees that the products the subject of the contract shall be free from defects including components and manufacture and specifications of the contract The warranty period is 12 months from the date the goods the subject of the contract are despatched from the Seller s premises The warranty is app...

Страница 24: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 24 ...

Отзывы: