Cod.Doc.2550041-REV 2.2.0 gb.doc
Pagina 19
Cable connection and fixing power on contactor’s terminals and output terminals, must be in accordance to following data
Contactor (check the type
installed in the panel)
Minimum and maximum section
of the cables connected without
terminals
Minimum and maximum terminals fixing power .Warning!!! During
the power cables connection, don’t move the auxiliary wires from
the contactor terminals and check if they are properly fixed
togheter with power cables in the terminals.
Tipo mm
Nm Ibft
BF9T
1-6 1,5-1,8
1,1-1,5
BF12T
1-6 1,5-1,8
1,1-1,5
BF18T
1-6 1,5-1,8
1,1-1,5
BF26T
2,5-6 2,5-3 1,8-2,2
BF38T
2,5-16 2,5-3 1,8-2,2
CL04
2,5-16 1,4
1,02
WARNING !! If the installation of the product is not in accordance to the specifics descripted above, can cause problems in terms of
functionality and can also compromises warranty conditions. Then Tecnoelettra srl won’t be responsible for any direct or not direct
damage due to wrong installation.
POWER CONVERSION TABLE
Contactor Ith
thermal current
Panel maximum power
400Vac 3P+N
kVA max / I max
Panel maximum power
230Vac 3P+N
kVA max / I max
Panel maximum power
230Vac 1P+N
kVA max / I max
25A
17kVA / 25A
10kVA / 25A
9kVA / 40A
32A
22kVA / 32A
12kVA / 32A
11kVA / 50A
45A
31kVA / 45A
18kVA / 45A
16kVA / 72A
56A
38kVA / 56A
22kVA / 56A
20kVA / 89,5A
60A
42kVA / 60A
24kVA / 60A
22kVA / 96A
5 - AT206 PANEL PROGRAMMATION INSTRUCTION
5.1 - Programmation menu access description
With the board in RESET position, press TEST button for 5 seconds; after that, the entrance in the menu is showed by the display with the first code of
the parameter “U.01”.
This procedure permit to enter only in the “User menu”; that permits to modify only the normal use parameters (descripted in par. 5.3); by this you are
not able to enter in the technical parameters that can cause function problem in the panel (these parameters are descripted in par.5.4).
To have access to complete menu (advanced menu), you need a different password.
To have it, please contact the dealer or the manufacturer.
5.2 - Parameters modification instructions
TEST button permits to see the value of the parameter
START button permits to increase the value and STOP button permit to decrease the value. For the time setting, START button increase the hours
value and STOP button increase the minutes value.
To save the value set and exit from parameter, press RESET then AUT button. (In advanced menu only RESET button to save and exit)
To exit from parameter without saving, press AUT button.
MEAS button permits to change (increase) the number of the parameter in a menu
MAN button permits to change (increase) the number of the menu
At the end of the programmation, press AUT than RESET buttons to return definitively from programmation mode to operative mode.
5.3 - User menu parameters
Setup Description
Range Default
Group 1
Test
U.01
Automatic test interval time
1 – 30days
3 days
U.02
Test duration
1 – 30 min
10 min
U.03
Test start time
00:00 – 23:59
10:00
U.04
Test with load
0=with load 1=without load
1
Group2 Various
U.08
Siren relay closing time
0 – 60 sec
20 sec
U.09
Engine starting delay from EJP/T signal
0 – 99 min
25 min
U.10
Switching delay for EJP/T(1 wire)
0 – 30 min
5 min
Group3 Clock
setting
U.11
Time
00:00 – 23:59
11:11
Содержание AT206
Страница 1: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 1 ELECTRICAL PANEL AT206 AT206B USER MANUAL ...
Страница 15: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 15 4 2 AT206 panel electrical drawing ...
Страница 16: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 16 4 3 AT206B panel electrical drawing ...
Страница 17: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 17 4 4 Diesel engine auxiliary connection ...
Страница 18: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 18 4 5 Gasoline engine auxiliary connection ...
Страница 24: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 24 ...