Cod.Doc.2550041-REV 2.2.0 gb.doc
Pagina 9
2.3 - Panel wall mounting instructions
WARNING: THE INSTALLATION OF THE PANEL MUST BE MADE ONLY BY SKILLED PEOPLE
3 - FIRST STARTING OF THE PRODUCT, USE AND DESCRIPTION
3.1 - Operation to do during the first starting of the AT206 panel
When you supply for the first time the panel, the display shows “U11” flashing, to remember you the time programmation (User menu, parameter U11).
Press RESET button to stop this flashing and set the board in RESET position.
The non observance of the indications given about the first starting of the product, can cause faulty situations on the same product
Before the first starting of the panel, check that the indications on the “Identification data plate” (par. 2.1.1) are in accordance with the
characteristics of the present electrical system.
The programmation of time is needed
3.1.1 - How programming the time on the panel
To program the time, follow the procedure descripted below:
-
Press RESET button
-
With the board in RESET position, press TEST button for 5 seconds until the display shows “Set”; after that the display shows the first code of the
parameter “U.01 – Automatic test interval time”. To see all the parameters, please check the following table
-
By continously pressing of MEAS button, reach parameter “U.11” showed on the display. This parameter is about the actual time.
-
Press TEST button to see the value stored now.
-
Press START button to increase the value of the hour or press STOP button to increase the value of the minutes
-
When the time is correct, press RESET button to save it and press AUT button to return on the parameter code (the display shows U.11)
-
Press AUT button than RESET button to exit from menu and return to the normal function mode.
Setup Description
Range Default
Group 1
Test
U.01
Automatic test interval time
1 – 30days
3 days
U.02
Test duration
1 – 30 min
10 min
U.03
Test start time
00:00 – 23:59
10:00
U.04
Test with load
0=with load 1=without load
1
Group2 Various
U.08
Siren relay closing time
0 – 60 sec
20 sec
U.09
Engine departure delay from EJP/T start
0 – 99 min
25 min
U.10
Switching delay for EJP/T(1 wire)
0 – 30 min
5 min
Group3 Clock
setting
U.11
Time
00:00 – 23:59
11:11
For air flow reasons, it is necessary that
around the panel there is a free space of
about 10cm for all the perimeter
The panel must be fixed on the wall by
two fixing hook in equipment
.
Содержание AT206
Страница 1: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 1 ELECTRICAL PANEL AT206 AT206B USER MANUAL ...
Страница 15: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 15 4 2 AT206 panel electrical drawing ...
Страница 16: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 16 4 3 AT206B panel electrical drawing ...
Страница 17: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 17 4 4 Diesel engine auxiliary connection ...
Страница 18: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 18 4 5 Gasoline engine auxiliary connection ...
Страница 24: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 24 ...