3.4 - AT206 panel; function description 

 

BOARD IN RESET 

The generator can’t work. If the mains is ok, the mains contactor is closed. If the generator is running, when you change to this function mode the 
engine is stopped immediatly and the eventual alarms are resetted. The alarm can’t be resetted if the cause of alarm still remain. 
 

BOARD IN MANUAL 

The generator can be started and stopped only manually by START and STOP buttons; also the changeover switch function works from mains to 
generator and viceversa by MAINS and GEN buttons. 

 
BOARD IN AUTOMATIC 

The generator start automatically when there is a mains failure and stop automatically when the mains is ok. 

 
AUTOMATIC TEST 

Is enable only if the board is in automatic function. If enable, make a complete starting procedure in accordance to the programmation set. If the mains 
is ok, this test is without changeover switch on the generator contactor; if during this test there is a mains failure, automatically the board close the 
generator contactor to supply the load by the generator. The stop procedure begin only when the mains come back to correct values. 
 

ALARMS 

When there is an alarm, the display shows an identification code about the problem: on the label of the boards there is a list with alarms code and 
description. By RESET button you can reset the alarms and by this you prevent an involuntayr restart of the generator. If the alarm on the display 
doesn’t disappear, you have to remove the cause of the alarm. 
 

3.4.1 - Procedure to setting tha automatic test 

 

   

It’s strongly reccomended the enabling of the automatic test to prevent problems caused by a long inactivity of the generator 

 

To enable the automatic test, please follow the instruction below: 

Press RESET button 

With the board in RESET position, press TEST button for 5 seconds until the display shows “Set”; after that the display shows the first code of the 
parameter “U.01 – Automatic test delay time”. To see all the parameters, please check the following table 

Press TEST button to see the value stored now, then press START button to increase this value or STOP button to decrease it. When the value is 
correct, press RESET button to save the modification and press AUT to exit from parameter. This parameter specifies the delay from one automatic 
test and the next one. If you don’t press RESET before exit by pressing AUT, modifications made on the parameter won’t be saved. 

By pressing MEAS button, go to parameter “U.02” showed on the display. Press TEST button to see the value stored now, then by START button  
(increase) or STOP button (decrease) change the duration time of the automatic test. When the value is correct, press RESET then AUT button. 

By pressing MEAS button, go to parameter “U.03” showed on the display. Press TEST button to see the value stored now, then by START button  
increase the hours value or by STOP button increase the minutes value to change the starting time of the automatic test. When the value is correct, 
press RESET then AUT button. 

By pressing MEAS button, go to parameter “U.04” showed on the display. Press TEST button to see the value stored now, then by START button  
(increase) or STOP button (decrease) it; change if you want the automatic test with changeover switch (set it to “0”) or without changeover switch (set 
it to “1”).  When the value is correct, press RESET then AUT button. 

At the end, press AUT then RESET button to exit from menu and to return to the normal operating mode. 

 

When the automatic test parameters are set, you have to enable this test; with the board in automatic mode, keep pressed TEST untill the display 
shows “On” and the test led turn ON. From this moment the board starts the counting of the time to make the first test. This test will begin after the set 
days in parameter “U.01”, at the set time in parameter “U.03” and for a set duration in parameter “U.02”. To disable the automatic test, with the board in 
AUT position keep pressed TEST button untill the display shows “Off” and the test led turn off. 

 
 

EXAMPLE: 

 

Setup Description 

Range  Default 

 

 

 

 

Group 1 

Test 

 

 

U.01 

Automatic test interval time 

1 – 30days 

3 days 

U.02 

Test duration 

1 – 30 min 

15 min 

U.03 

Test start time 

00:00 – 23:59 

10:00 

U.04 

Test with load 

0=load    1=a vuoto 

 
 
If you enable the automatic test with TEST button on Monday afternoon at 15.00, first test will start 3 days after (on Thursday) from 10.00 to 10.15. 
Second test will start on next Sunday (3 more days later) always from 10.00 to 10.15 
 
 
 
 
 
 
 
 
 
 

Содержание AT206

Страница 1: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 1 ELECTRICAL PANEL AT206 AT206B USER MANUAL ...

Страница 2: ...ption 9 3 1 Operation to do during the first starting of the AT206 panel 9 3 1 1 How programming the time on the panel 9 3 2 AT206 panel LED indication decription 10 3 3 AT206 panel command buttons decription 10 3 4 AT206 panel function description 11 3 4 1 Procedure to setting tha automatic test 11 4 AT206 connection and electrical drawings 12 4 1 Power connection 12 4 1 1 Triphase connection 400...

Страница 3: ... initial performance and safety required by current standards are restored Use of non genuine spare parts shall immediately forfeit all right to warranty and Technical Service by TECNOELETTRA The special composition and design of this panel enables satisfying the most restrictive operator safety standards To use TECNOELETTRA Electric Panels in the best way below we give the most important rules to...

Страница 4: ...equence please make sure that these levels are complied with As concerns atmospheric conditions the prescriptions contained in the CEI EN 60439 1 6 1 2 have to be complied with Check that the information on the control panel identification plate is compatible with appliance ratings such as voltage current frequency etc If the control panel can be locked make sure that only authorised personnel can...

Страница 5: ...on is given by the flow of energy passing through the control components and by the management of the electric control panel 1 7 Cautions levels Below we give the symbols used in the manual to draw the reader s attention to the different levels of danger in the Use and Maintenance of the electric panel DANGER Information or procedures that unless carried out meticulously cause death or serious inj...

Страница 6: ... country it is destined for CAUTION In addition it is wise to destroy the machine s identification plate and any other documents 1 12 Assistance center All maintenance work and technical service must be performed by Specialized personnel authorized by TECNOELETTRA who will arrange for a technician to step in after the customer s call 1 13 Repairs and spare parts For any further inconveniences not ...

Страница 7: ...e The technical plate is secured on the outside of the electric panel it gives the main particulars and certifies its conformity with the EEC machine directive 89 392 attachment H Therefore its CE marking is valid only when mounted with machines made in accordance with the provisions of the EEC machine directive 89 392 and subsequent amendments introduced 91 368 EEC 83 44 EEC 93 68 EEC Every time ...

Страница 8: ...N IN EMERGENCY SITUATION PRESS THIS BUTTON TO STOP IMMEDIATLY THE GENERATOR Control board Predisposition for magnetothermic switch or earth failure relay IMP switch to supply 230Vac for auxiliary output OPTIONAL Buzzer B for acoustic alarm Input for generator power connection Input for mains power connection Output for load power connection Auxiliary connector CN1 Auxiliary connector CN2 F1 F4A F2...

Страница 9: ... display shows the first code of the parameter U 01 Automatic test interval time To see all the parameters please check the following table By continously pressing of MEAS button reach parameter U 11 showed on the display This parameter is about the actual time Press TEST button to see the value stored now Press START button to increase the value of the hour or press STOP button to increase the va...

Страница 10: ...he board is in AUTOMATIC Par 3 4 If on it indicates that the board is in RESET Par 3 4 It permit to activate the automatic test Par 3 4 Board in MANUAL function Par 3 4 It permit to change the type of measurement showed by the display It permit to close the mains contactor active only in MANUAL function press it with MAN button in the same time It permit to close the generator contactor active onl...

Страница 11: ...P button to decrease it When the value is correct press RESET button to save the modification and press AUT to exit from parameter This parameter specifies the delay from one automatic test and the next one If you don t press RESET before exit by pressing AUT modifications made on the parameter won t be saved By pressing MEAS button go to parameter U 02 showed on the display Press TEST button to s...

Страница 12: ... T3 T4 Load connection X0 Terminals sequence U V W N Generator phase 1 T1 Generator phase 2 T2 Generator phase 3 T3 Generator neutral T4 Common earth connection Genarator Mains Load Mains phase 1 T1 Mains phase 2 T2 Mains phase 3 T3 Mains neutral T4 Phase 1 load U It pass through TA before connection to load terminal U Phase 2 load V Phase 3 load W Neutral load N Amperemetric Transformer TA WARNIN...

Страница 13: ...T2 Generator phase 3 T3 Generator neutral T4 Common earth connection Genarator Mains Load Mains phase 1 T1 Mains phase 2 T2 Mains phase 3 T3 Mains neutral T4 Phase 1 load U It pass through TA before connection to load terminal U Phase 2 load V Phase 3 load W Neutral load N Amperemetric Transformer TA Warning Move blue wire n 14 from terminal T4 to terminal T3 Warning Move blue wire n 24 from termi...

Страница 14: ...poles T3 and T4 must be connected togheter T3 T4 Neutral By this connection the max current of the contactor is Ith x 1 6 Generator phase to use maximum contactor power poles T1 and T2 must be connected togheter T1 T2 phase By this connection the max current of the contactor is Ith x 1 6 Mains phase to use maximum contactor power poles T1 and T2 must be connected togheter T1 T2 phase By this conne...

Страница 15: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 15 4 2 AT206 panel electrical drawing ...

Страница 16: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 16 4 3 AT206B panel electrical drawing ...

Страница 17: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 17 4 4 Diesel engine auxiliary connection ...

Страница 18: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 18 4 5 Gasoline engine auxiliary connection ...

Страница 19: ...ntrance in the menu is showed by the display with the first code of the parameter U 01 This procedure permit to enter only in the User menu that permits to modify only the normal use parameters descripted in par 5 3 by this you are not able to enter in the technical parameters that can cause function problem in the panel these parameters are descripted in par 5 4 To have access to complete menu ad...

Страница 20: ... 01 Stop times electromagnet closing time gasoline engine stop time 1 30sec 10 02 Decelerated funct time 1 60 sec 30 03 Cooling time 1 300sec 120 Group 4 Protections P4 01 Minimum frequency fixed delay 5sec 80 100 90 02 Maximum frequency overspeed 100 120 110 03 Maximum frequency al tripping delay 0 15 sec 2 sec 04 Battery minimum frequency 7 12V 9 05 Battery maximum frequency 13 17V 17V 06 Load m...

Страница 21: ... 0001 0001 yes A2 05 Not used 0000 0001 0000 no A3 Avaria meccanica 0000 0001 0001 yes A3 01 Stop without cooling 0000 0001 0001 yes A3 02 Stop with cooling 0000 0001 0000 no A3 03 Siren relay 0000 0001 0001 yes A3 04 Alarm relay if enabled 0000 0001 0001 yes A3 05 Not used 0000 0001 0000 no A4 500 rpm failure strap breaking 0000 0001 0001 yes A4 01 Stop without cooling 0000 0001 0000 no A4 02 Sto...

Страница 22: ...Battery maximum voltage 0000 0001 0001 yes A12 01 Stop without cooling 0000 0001 0000 no A12 02 Stop with cooling 0000 0001 0001 yes A12 03 Siren relay 0000 0001 0001 yes A12 04 Alarm relay if enabled 0000 0001 0001 yes A12 05 Not used 0000 0001 0000 no A13 Starting failure 0000 0001 0001 yes A13 01 Stop without cooling not influential always as set to no 0000 0001 0000 no A13 02 Stop with cooling...

Страница 23: ...egularly stipulated in the contract PACKING It is always gratis WARRANTY AND GUARANTEE The Seller guarantees that the products the subject of the contract shall be free from defects including components and manufacture and specifications of the contract The warranty period is 12 months from the date the goods the subject of the contract are despatched from the Seller s premises The warranty is app...

Страница 24: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 24 ...

Отзывы: