2.1.8
ONE-MAN WALK TEST MODE
▪
The following procedure is used to put a zone into Test Mode:
Press and hold
for 3 seconds.
The Test LED and Zone 1 Fault /In Test/Disable LED will both flash rapidly
Yellow.
Press
to move on to the zone to
be tested.
Each press will advance the selection onto the next zone (i.e., two presses
will select zone 3) and this will be confirmed by the respective Zone Fault/In
Test/Disable LED flashing rapidly.
Confirm your selection by pressing
once.
The Test LED and the selected z
one’s Fault/In Test/Disable LED will now
be flashing fast Yellow.
To exit the walk test selection mode, wait for 10 seconds or press reset.
▪
The same procedure is used to remove a zone from Test Mode. Alternatively, for a quick exit from
Test Mode, push the Reset button.
When a zone is in test, the Fire LED for that zone, the General Fire LED, Buzzer, and all Sounders will go on
for eight seconds before automatically clearing the condition if the device in the field has been reset.
No relays will activate if a zone is in test, except those relays programmed to switch when Sounders are
Activated.
2.1.9
ADVANCED CONTROLS AND INDICATIONS
Symbol
Function
LED Indication
Description
Service Switch
General Disable Flashing Yellow.
Sounder Fault/Disable Flashing
Yellow.
Enable Controls Flashing Yellow.
Used to place panel in Service/Commission
mode. All outputs are disabled when the
switch is activated.
Boot Loader
Jumper
System Fault Flashing Yellow.
Used to place the panel in Boot loader mode
to upgrade panel firmware.
No control or circuits will be active in this
mode. A hardware reset is required to revert
to Normal.
Figure 30
Service Switch
NB:
The switch must be in the left position for normal operation.