ORYX202 ORYX204 ORYX208 Conventional Fire Panels
– INSTALLATION & OPERATION MANUAL
PRMAN-0047 ORYX200 S21 Fire Panel Range Rev 02.00 220224.docx
E&OE
- 37 -
3.1.4
INPUTS
The Inputs have the following programmable features:
Programming Group
Programming
Function
Comments
Options
None
None
The input is not used.
None
General
External Fault
Activating an input with this setting will register a
general fault condition on the panel.
Input Text: 0
–21
Characters
Enabled: YES/NO
Test: YES/NO
Inverted: YES/NO
Reset
Activating an input with this setting will cause
the panel to be reset (if permitted). Input 1
default to this setting.
Input Text: 0
–21
Characters
Enabled: YES/NO
Test: YES/NO
Inverted: YES/NO
Silence Alarm
Activating an input with this setting will cause all
sounders on the panel to be silenced.
Input Text: 0
–21
Characters
Enabled: YES/NO
Test: YES/NO
Inverted: YES/NO
Sound Alarm
Activating an input with this setting will cause
the buzzer and all the sounders on the panel to
be activated.
Input Text: 0
–21
Characters
Enabled: YES/NO
Test: YES/NO
Inverted: YES/NO
Silence Buzzer
Activating an input with this setting will cause
the buzzer to be silenced.
Input Text: 0
–21
Characters
Enabled: YES/NO
Test: YES/NO
Inverted: YES/NO
Mute
Activating an input with this setting will cause
the buzzer and all sounders on the panel to be
silenced. Input 2 default to this setting.
Input Text: 0
–21
Characters
Enabled: YES/NO
Test: YES/NO
Inverted: YES/NO
External Controls
Enabled
Activating an input with this setting will enable
Level 2 control keys.
Input Text: 0
–21
Characters
Enabled: YES/NO
Test: YES/NO
Inverted: YES/NO
External Supervisory Activating an input with this setting will cause
the sounder to activate on the panel. The
sounder will remain on until the input is
deactivated. Repeater input 2 defaults to this
setting.
Input Text: 0
–21
Characters
Enabled: YES/NO
Test: YES/NO
Inverted: YES/NO
External Supply Fault Activating an input with this setting will register a
general fault condition on the panel. Repeater
input 1 defaults to this setting.
Input Text: 0
–21
Characters
Enabled: YES/NO
Test: YES/NO
Inverted: YES/NO