ORYX202 ORYX204 ORYX208 Conventional Fire Panels
– INSTALLATION & OPERATION MANUAL
PRMAN-0047 ORYX200 S21 Fire Panel Range Rev 02.00 220224.docx
E&OE
- 28 -
2
OPERATION
2.1
INTRODUCTION
2.1.1
ACCESS LEVELS
The panel operation is protected from inadvertent and erroneous misuse by means of three access levels.
These levels are as follows:
▪
Level 1:
Untrained User
– An Untrained User will only be able to silence the buzzer.
▪
Level 2:
Authorised User (Enable Controls key switch)
– An Authorised User will be able to use all control
buttons on the panel membrane.
▪
Level 3:
Commissioning, Service and Maintenance
– Opening the panel and connecting via USB port for
programming, Event Log retrieval, or Enabling the Service Switch.
2.1.2
FRONT PANEL CONTROLS AND INDICATIONS
Figure 29
Front Panel Controls & Indications shown for the 4 Zone Panel (ORYX204)