104
7.12.2 Instrument Subsystem
The subsystem programs one or more power supplies. <NR1> from 1 to 31.
INSTrument:COUPle
SCPI Command Syntax
INSTrument:COUPle <CRD>
GEN Command Syntax
None
Parameters
ALL|NONE
INSTrument:NSELect
SCPI Command Syntax
INSTrument:NSELect <NRf>
GEN Command Syntax
ADR n (single address)
Examples
INSTrument:NSELect 6
Query Syntax
INSTrument:NSELect?
7.12.3 Voltage Subsystem
VOLTage
Sets the output voltage value in Volts. The range of voltage values are described in Table 7-5. The
maximum number of characters is 12.
SCPI Command Syntax
[SOURce]:VOLTage[:LEVel] [:IMMediate][:AMPLitude] <NRf+>
GEN Command Syntax
PV < NRf+> PV?
Default Suffix
V
*RST Value
0
Examples
:VOLT 500 MV
VOLT:LEV 234.56789
Query Syntax
[SOURce]:VOLTage[:LEVel][:IMMediate][:AMPLitude]?
VOLTage? MAX VOLTage? MIN
Returned Parameters
<NR3> VOLT? returns the present programmed voltage level.
VOLT? MAX and VOLT? MIN returns the maximum and minimum programmable
voltage levels.
VOLTage:MODE
This command selects FIX, LIST, WAVE subsystems control over the power supply output voltage.
SCPI Command Syntax
[SOURce]:VOLTage:MODE <CRD>
GEN Command Syntax
None
Parameters
NONE | FIXed | LIST | WAVE
*RST Value
NONE
Examples
VOLT:MODE LIST VOLT:MODE FIX
Query Syntax
[SOURce]:VOLTage:MODE?
Returned Parameters
NONE | FIX | LIST | WAVE
Содержание Z160-1.3
Страница 5: ...This page intentionally left blank...
Страница 27: ...26 Pages 26 33 are reserved for Z600 800W...
Страница 28: ...27 Pages 26 33 are reserved for Z600 800W...
Страница 29: ...34 2 6 Z200W 400W 600W 800W Outline Drawing...
Страница 30: ...35 2 7 Z200W 400W 600W 800W Optional IEEE Isolated Analog Interface Outline Drawing...
Страница 31: ...36 This Page intentionally left blank...
Страница 137: ...NOTES...
Страница 138: ...NOTES...
Страница 139: ...NOTES...