background image

 

86 

83532002 Rev H 

8.9. Fast Queries 

These are commands that read a response very quickly from the Power Supply. They use 
unprintable character codes. They allow the Power Supply to avoid the normal command 
processing delays. 

The processing time for these queries is typically 2ms, so total query speed is 2ms plus the 
RS-232/RS-485 transmission time. 

Since these queries embed the power supply address (0 to 30), there is no need to first send 
the “

ADR n

” addressing command. 

8.9.1.  Fast Test for Connection 

This is an addressed query that is good for scanning to see what power supplies are “on 
line”. If no response is returned within 10ms, the control program has determined that no 
Power Supply is connected at that address. 

Query Format: 

Send two bytes of unreadable characters. First: 
Byte 1 = 1010 1010 = AA hex 
Byte 2 = 000x xxxx  

(where xxxxx is the address of the supply in binary) 

Query Response: 

The power supply returns 5 characters: 

First a   “1” = 31 hex if Multi-drop is enabled  
   or a  

“0” = 30 hex if Multi-drop is not enabled 

Then four printable characters: 

Dollar sign “$” 
Checksum (two ASCII hex characters) = “30” or “31” 
Carriage-return terminator 

8.9.2.  Fast Read Registers 

This query allows fast polling of the status and error registers for many power supplies on 
a RS-232/RS-485 link. It is useful for checking many supplies to verify they are all 
operating as expected. 

Query Format: 

Send two bytes of unreadable characters. First: 

100x xxxx  

(where xxxxx is the address of the supply in binary) 

And send it a second time: 

100x xxxx 

send 2 characters sequentially 

Query Response: 

The power supply returns 16 characters including the contents of the status and 
fault registers (see Section 8.11 and Figure 8-7). 
First twelve bytes contain binary data from six registers: 

STAT?   SENA?   SEVE?   FLT?   FENA?   FEVE? 

Then four printable characters: 

Dollar sign “$” 
Checksum (two ASCII hex characters) 
Carriage-return terminator 

Содержание GENESYS 15KW

Страница 1: ...ESYSTM 10KW 15KW Programmable DC Power Supplies Document 83 532 002 Rev J TDK Lambda Americas Inc Programmable High Voltage 405 Essex Road Neptune NJ 07753 Tel 1 732 795 4100 Fax 1 732 922 9334 www us...

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ......

Страница 6: ...lti drop refer to the IEMD User s Manual P N 83 030 200 For units equipped with the LAN option for Local Area Network with Multi drop refer to the LAN User s Manual P N 83 034 100 For units equipped w...

Страница 7: ...Signals 23 2 7 Front Panel 24 2 8 Software Spec 24 2 9 Digitial Programming And Readback 25 2 10 Mechanical Construction 25 2 11 Environmental Conditions 25 2 12 EMC 26 2 13 Safety 26 2 14 J1 Connect...

Страница 8: ...r Panel J1 Connector 53 5 8 Enable Disable Control via Rear Panel J1 Connector 54 5 9 CV CC Signal 54 5 10 PS_OK Signal 54 5 11 Safe Start and Auto Restart Modes 55 5 12 Front Panel Locking 55 5 13 Ov...

Страница 9: ...mands 83 8 9 Fast Queries 86 8 10 Status and Error Commands 87 8 11 Status Error and SRQ Registers 88 8 12 Serial Communication Test Set Up 91 9 ISOLATED ANALOG PROGRAMMING OPTION 93 9 1 Introduction...

Страница 10: ...Americas Inc for warranty service the buyer shall prepay shipping charges to TDK Lambda Americas Inc If the unit is covered under the foregoing warranty then TDK Lambda Americas Inc shall pay the shi...

Страница 11: ...potential shock hazard that might cause personal injury WARNING OUTPUT TERMINALS GROUNDING There is a potential shock hazard at the RS 232 RS 485 LAN IEEE and the USB ports when using power supplies w...

Страница 12: ...ing procedure correctly could result in personal injury A WARNING sign should not be skipped and all indicated conditions must be fully understood and met The CAUTION sign denotes a hazard An attentio...

Страница 13: ...ch e il y a un risque de choc lectrique pouvant provoquer des blessures ATTENTION DANGER MISE A LA TERRE DES BORNES DE SORTIE Il y a un danger de choc lectrique sur les ports RS 232 RS 485 LAN IEEE et...

Страница 14: ...ttire l attention sur une proc dure Si la proc dure n est pas suivie correctement il peut en r sulter des blessures Le symbole WARNING Attention danger ne doit pas tre ignor et toutes les conditions i...

Страница 15: ...ERDUNG DER AUSGANGSANSCHL SSE Es besteht die Gefahr von m glichen Schl gen an der RS 232 RS 485 LAN IEEE und den USB Anschl ssen wenn Netzger te mit h heren Nenn oder kombinierten Spannungen als 400V...

Страница 16: ...haden f hren Eine WARNUNG darf nicht bergangen werden und alle angezeigten Umst nde m ssen vollkommen verstanden und eingehalten werden Das VORSICHTSYMBOL deutet auf eine Gefahr hin Die Aufmerksamkeit...

Страница 17: ...porteranno al rischio di scossa elettrica e di conseguente potenziale infortunio AVVERTENZA MESSA A TERRA DEI TERMINALI DI USCITA Vi rischio di scossa elettrica in corrispondenza delle porte R S232 R...

Страница 18: ...nfortunio Non ignorare alcun simbolo di AVVERTIMENTO Tutte le condizioni indicate devono essere pienamente comprese e rispettate Il simbolo di ATTENZIONE denota un pericolo necessario prestare attenzi...

Страница 19: ...o Qualquer interrup o do condutor de terra de protec o ou corte do terminal de terra de protec o poder originar um risco de choque pass vel de provocar ferimentos AVISO LIGA O TERRA DE TERMINAIS DE SA...

Страница 20: ...a o O sinal de AVISO assinala um perigo Solicita se aten o para um procedimento N o seguir correctamente o procedimento pode resultar em ferimentos N o se deve ignorar um sinal de AVISO e todas as con...

Страница 21: ...conductor de tierra de protecci n o desconexi n del borne de tierra de protecci n supondr un riesgo potencial de descarga el ctrica que puede llegar a causar da os personales WARNINGADVERTENCIA CONEXI...

Страница 22: ...NCIA indica un peligro Llama la atenci n ante un procedimiento Si el procedimiento no se realiza correctamente podr an producirse lesiones personales Los s mbolos de ADVERTENCIA no se pueden pasar por...

Страница 23: ...r to set the output parameters the protections levels Over Voltage protection Under Voltage limit and Foldback and preview the settings The rear panel includes the necessary connectors to control and...

Страница 24: ...easurement f Foldback protection setting g Over voltage protection setting and readback h Under Voltage limits setting and readback i Power Supply start up mode last setting or safe mode 1 2 5 Analog...

Страница 25: ...energized load is disconnected from the Output See Section 3 9 for details CAUTION Observe all torque guidelines within this User s Manual Over torqueing hardware may damage the unit or accessories Su...

Страница 26: ...4 Analog Meters are NOT available Note 5 Factory Installed LAN IEMD USB IS510 or IS420 may not be installed together Limit one 1 per Power Supply EXAMPLES GEN10 1000 3P208 GEN10 1000 IEMD 3P400 GEN10...

Страница 27: ...5 EN60950 1 max 9 Input Protection Circuit breaker for 7 5V 10V and 12 5V Outputs 10kW with 208VAC input 10 Fuse Fuse for 7 5V 10V and 12 5V Outputs 10kW with 400VAC 480VAC input Fuse for 20V Vout 600...

Страница 28: ...shall always be less than 95 of the Output voltage setting Raises the PS_OK signal when Vout is below limit Does not affect J1 Remote Analog programming Default 0V 14 Input Under Voltage protection Y...

Страница 29: ...h Single Wire connection for Output Voltage Models where 7 5V Vout 25V 10kW In Advanced Parallel mode the Master displays the calculated not actual Output current for the combined parallel combination...

Страница 30: ...emote sense VOLT Display PREV setting for Vout Actual Vout OVP UVL settings SAF AUT Restart mode OUT OFF or fault LFP UFP setting RS 232 RS 485 Address setting IEEE or LAN Enabled and Address CURR Dis...

Страница 31: ...AMP 747461 5 Female on Power Supply Male on Mating connector 747321 Standard 25 pin Sub D connector 4 RS 232 RS 485 STD RJ 45 Phone Jack connector 5 Isolated Analog Option refer to Isolated Analog Op...

Страница 32: ...4 3 10V m 6 Power Frequency Magnetic Field EN61000 4 8 30A m 7 Conducted emission EN55011A FCC part 15J A 8 Radiated emission EN55011A FCC part 15J A Note EMC Approval for Vout 30V 208VAC 400VAC 30V V...

Страница 33: ...mon for VMON IMON CV CC LOC REM signal and P 2 Wire Parallel method only Connected internally to the negative local sense LS J1 13 CV CC Output for Constant Voltage Constant Current mode indication J1...

Страница 34: ...on Initial physical inspection of the Power Supply Section 3 3 2 Installation Installing the Power Supply Ensuring adequate ventilation Section 3 4 Section 3 5 3 AC source AC source requirements Conne...

Страница 35: ...panel and the exhaust is at the rear panel Upon installation allow cooling air to reach the front panel ventilation inlets Unrestricted air space at the front and the rear of the unit is necessary for...

Страница 36: ...to Chassis per Section 3 9 of this User s Manual and wait 5 minutes before removing top cover The Power Supply AC On Off switch is not the main disconnect device and does not completely disconnect all...

Страница 37: ...s indicated in the procedure 3 8 2 Prior to Operation a Ensure that the Power Supply is configured to the default setting AC On Off switch at the Off position Dip switch SW1 All positions at Down Off...

Страница 38: ...m zero to the maximum rated Output current for the Power Supply model Compare the DVM reading with the front panel CURRENT display to verify the accuracy of the CURRENT display Ensure that the front p...

Страница 39: ...proximately 10 of the unit Output current rating d Momentarily press the FOLD button Ensure that the FOLD LED illuminates The Output voltage should remain unchanged e Increase the load current from 5...

Страница 40: ...rrent settings to zero Verify these settings using the front panel PREView button 3 Verify the energized load is disconnected by noting the front panel display measurements are close to zero volts and...

Страница 41: ...put Voltage Range 7 5V 80V 100V 300V Vertical Bus Bar Configuration 0 422 inch mounting hole 7 5V 25V models have two mounting holes 30V 300V models have one mounting hole Use 3 8 inch diameter bolt n...

Страница 42: ...the load could make the ripple and noise at the load worse than the noise at the power supply rear panel output Additional filtering with bypass capacitors at the load terminals may be required to byp...

Страница 43: ...Remote sensing is used when in Constant Voltage mode the load regulation is important at the load terminals Use twisted or shielded wires to minimize any noise pick up If shielded wires are used the...

Страница 44: ...cated output distribution terminals are used the Power Supply output terminals should be connected to the distribution terminals by a pair of twisted and or shielded wires Each load should be separate...

Страница 45: ...or voltage drop on the load wires therefore it is recommended only for low load current applications or where the load regulation is less critical WARNING All models shall not float outputs more than...

Страница 46: ...J2 1 Remote positive sense S J2 2 Local positive sense Connected internally to the positive output terminal LS J2 3 Not connected NC J2 4 Local negative sense Connected internally to the negative out...

Страница 47: ...Off power switch to the On position NOTES 1 If the power supply is operating in remote sense and either the positive or negative load wire is not connected an internal protection circuit will activat...

Страница 48: ...connectors terminals Section 4 2 Front Panel Controls and Indicators Section 4 3 Rear Panel Connections and Controls 4 2 Front Panel Controls and Indicators See Figure 4 1 to review the controls indi...

Страница 49: ...T button Main function Output ON OFF control Press OUT to set the output On or Off Press to reset and turn On the output after OVP or FOLD alarm events have occurred Auxiliary function Selects between...

Страница 50: ...hold PREV button to toggle between Locked front panel and Unlocked front panel The display will cycle between LFP and UFP Releasing the PREV button while one of the modes is displayed selects that mo...

Страница 51: ...ions about the rear panel connections and controls Safety PE GND must be connected 10kW Platform A Output Range 7 5V 25V 10kW 15kW Platform A B Output Range 30V 300V 7 6 5 4 3 8 1 10 2 7 6 5 4 3 8 1 1...

Страница 52: ...cludes Output voltage and current programming and monitoring signals Shut off control electrical signal Enable Disable control dry contact Power Supply OK PS_OK signal and operation mode CV CC signal...

Страница 53: ...ry default UP SW1 1 Output Voltage Remote Analog Programming Output Voltage Programmed by Front Panel Output Voltage Programmed by remote analog External Voltage SW1 2 Output Current Remote Analog Pro...

Страница 54: ...nnect the shield to a Power Supply Chassis ground screw 4 5 1 Making J1 Connections J1 connector type AMP P N 747461 3 J1 plug description AMP P N 745211 7 or 8 Wire dimension range AWG26 22 Extractio...

Страница 55: ...e 7 6 J1 12 COM Control Common Return for VMON IMON CV CC LOC REM Connected internally to the negative local sense LS potential J1 13 CV CC Output for Constant Voltage Constant Current mode indication...

Страница 56: ...rrent varies as required by the load b While the Power Supply operates in Constant Voltage mode the VOLTAGE LED on the front panel is illuminated c Adjustment of the Output voltage can be made when th...

Страница 57: ...Power Supply operates in Constant Voltage mode while the load current is increased to greater than the Output current limit setting the Power Supply will automatically switch to Constant Current mode...

Страница 58: ...Setting the UVL can be made when the Power Supply output is Enabled On or Disabled Off To set the UVL level press the OVP UVL button TWICE so that the CURRENT meter shows UUL The VOLTAGE meter shows t...

Страница 59: ...The Output On Off can be activated from the front panel using the OUT button or from the rear panel J1 connector The OUT button can be pressed at any time to enable or disable the Power Supply output...

Страница 60: ...her than 30VDC Always connect the CV CC signal to a voltage source with a series resistor to limit the sink current to less than 10mA 5 10 PS_OK Signal The PS_OK signal indicates a fault condition in...

Страница 61: ...led and the Output voltage and Output current are zero To enable the output and restore the last Output voltage and current limit values momentarily press the OUT button 5 12 Front Panel Locking The f...

Страница 62: ...OUT button or send OUT ON command via the serial port b Auto Restart mode In Auto Restart mode the Power Supply recovers to its last setting automatically when the Over Temperature condition is remov...

Страница 63: ...ems like it can be used to adjust the Output settings it is the Remote Analog control lines that actually set the programming limits 6 1 Series Operation Power supplies of the SAME MODEL can be connec...

Страница 64: ...l The Shut Off and PS_OK circuits are referenced to the isolated interface common IF_COM J1 2 3 The IF_COM terminals of different units can be connected together to obtain a single control circuit for...

Страница 65: ...circuits used to control series connected unit must be separated and floated from each other 2 Using the SO function and PS_OK The Shut Off and PS_OK circuits are referenced to the isolated interface...

Страница 66: ...e by making the Master unit display the calculated sum of all unit Output currents while the Slave units s Front Panel displays are disabled 6 2 1 Basic Parallel Operation In this method setting the u...

Страница 67: ...ge at the programmed Output Voltage Connect the sensing circuit to local or remote sensing as shown in Fig 6 7 or Fig 6 8 Master Single Wire Method Set the Master unit Output Voltage to the desired vo...

Страница 68: ...he Output Voltage of the Master unit to prevent interference with the Master unit s control The Output Current setting of each Slave unit is programmed by the Master unit to the desired load current d...

Страница 69: ...programmed to a higher value than the Master OVP setting which should prevent the Slave unit from shutting down before the Master unit does Thus when the Master unit shuts down due to an OVP conditio...

Страница 70: ...ire resistance should be as close as possible to each other to achieve current balance between power supplies 6 2 2 Advanced Parallel Operation Two Wire Single Wire Method In this method multiple supp...

Страница 71: ...ton by RS232 is not activated for Slave units 2 Connection to the Load Two Wire Method In parallel operation power supplies can be connected for local or remote sensing Refer to Fig 6 7 and 6 8 for ty...

Страница 72: ...ers will automatically set the following Output Voltage to approximately 102 of rated Output Voltage Programmed Current to zero UVL to zero volts OVP to its maximum value AST ON OUT ON Foldback Protec...

Страница 73: ...power Off to store the new setting s e After exiting from Slave operation the unit s parameters will be set to Programmed Voltage to zero Programmed Current to zero UVL to zero volts OVP to its maxim...

Страница 74: ...ote Sensing Two Wire Method Figure 6 9 Parallel Connection with Local Sensing Single Wire Method CAUTION Make sure that the connection between V terminals is reliable to avoid disconnection during ope...

Страница 75: ...69 83532002 Rev H Figure 6 10 Parallel Connection with Remote Sensing Single Wire Method...

Страница 76: ...Sense LS as it may damage the power supply CAUTION When the Isolated Analog Option is installed do not apply any signals to the non isolated VPGM and IPGM J1 9 and J1 10 pins All other J1 features may...

Страница 77: ...onnector Perform the following procedure to set the Power Supply to Remote Voltage programming a Turn the AC On Off power switch to the OFF position b Set SW1 1 to the UP position for Output voltage e...

Страница 78: ...GM J1 10 UP 0 10V 0 10V DOWN 0 5V 0 5V Table 7 3 SW1 3 Setting and Programming Range Remote Voltage PGM 1 14 1 25 10 12 8 9 23 22 OUTPUT CURRENT PROGRAMMING OUTPUT PROGRAMMING J1 connector rear panel...

Страница 79: ...ng mode e Connect a wire jumper between J1 8 and J1 12 refer to Table 4 4 f Connect the programming resistors to the mating plug of J1 as shown in Fig 7 2 g Set the programming resistors to the desire...

Страница 80: ...Up IMON Iout monitor J1 24 Table 7 5 Monitoring Signals Setting Notes 1 Radiated emissions FCC requirements FCC requirements for radiated emissions use shielded cable for the analog control signals an...

Страница 81: ...LTAGE display will then indicate the communication port Address c Using the VOLTAGE adjust encoder select the unit Address 0 to 30 d After 3 seconds of idleness the front panel display will revert and...

Страница 82: ...d the Power Supply will reply and remain in Local mode If a command that affects the output is received the Power Supply will perform the command and change to Remote mode 8 2 7 Front Panel in Remote...

Страница 83: ...N NO PIN NO NAME NAME SHIELD TX RX SG SHIELD RX TX SG DB 25 CONNECTOR 8 PIN CONNECTOR REMARKS TWISTED PAIR 8 1 13 1 2 3 5 7 8 1 PIN NO HOUSING HOUSING PIN NO NAME NAME SHIELD RX TX SG SHIELD TX RX SG...

Страница 84: ...ata format Serial data format is 8 bit one start bit and one stop bit No parity bit NOTE The address ADR n command must return an OK response before any other commands are accepted 8 5 2 Addressing Th...

Страница 85: ...to the Power Supply 8 6 Error Messages The Power Supply will return error messages for illegal commands and illegal programming parameters Refer to Table 8 1 for programming error messages and Table...

Страница 86: ...zero Remote non lockout remote Output current zero Auto start Off Output Off OVP maximum FOLD Off UVL zero The conditional registers FLT and STAT are updated the other registers are not changed 4 RMT...

Страница 87: ...0 FR 00 9 FILTER nn Set the low pass filter frequency of the A to D Converter for Voltage and Current Measurement where nn 18 23 or 46Hz default is 18Hz 10 FILTER Returns the A to D Converter filter f...

Страница 88: ...setting These settings are erased when the supply power is switched Off and the new last settings are saved 26 RCL Recalls last settings Settings are from the last power down or from the last SAV com...

Страница 89: ...own in Table 8 6 n may be up to 12 characters plus decimal point 3 GPC n Program the Output current value in amperes The range of Output current values is shown in Table 8 7 and 8 10 n may be up to 12...

Страница 90: ...25 0 500 0 0 500 0 500 20 0 0 20 0 600 0 0 600 0 600 17 0 0 17 0 Table 8 8 OVP Programming Range 10kW Table 8 9 UVL Programming Range 10kW Model Rated Output Voltage V Minimum V Maximum V Model Rated...

Страница 91: ...5 120 12 5 131 25 125 20 0 0 118 75 150 100 15 0 157 5 150 100 0 0 142 5 200 75 20 0 210 0 200 75 0 0 190 0 250 60 25 0 262 5 250 60 0 0 237 5 300 50 30 0 315 0 300 50 0 0 285 0 400 37 5 40 0 420 0 40...

Страница 92: ...address of the supply in binary Query Response The power supply returns 5 characters First a 1 31 hex if Multi drop is enabled or a 0 30 hex if Multi drop is not enabled Then four printable character...

Страница 93: ...re has to be developed enough to read messages that may come at any time and to recover if messages are corrupted by collisions If Service Request messaging is needed please contact TDK Lambda for ass...

Страница 94: ...mmand Response OK CV CC NFLT FLT AST FDE 0 LCL CV CC NFLT FLT 0 0 0 LCL 0 0 0 Status Registers Condition Enable Event Constant Voltage Constant Current No Fault Fault Auto Start Fold Enabled Spare Loc...

Страница 95: ...AT BIT Fault name Fault symbol Bit Set condition Bit Reset condition 0 LSB Constant Voltage CV Output is On and the supply in CV Output is ON and the supply is not in CV 1 Constant Current CC Output i...

Страница 96: ...when the fault clears the bit remains set Entire Event Register is cleared when user sends FEVE command to read the register CLS and power up also clear the Fault Event Register the Fault Event Regis...

Страница 97: ...Local Mode LCL Unit is set to Local by pressing front panel REM LOC button 8 12 Serial Communication Test Set Up Use the following instructions as basic set up to test the serial communication operati...

Страница 98: ...Power supply response OK PC write PV 5 0 Power supply response OK PC write PC 10 0 Power supply response OK Read back the Output voltage test PC write MV Power supply response 05 00 or voltage as see...

Страница 99: ...efficient ppm C 100 Output current programming temperature coefficient ppm C 100 Input impedance Ohm 1M Absolute maximum voltage VDC 0 15 Max voltage between program inputs and supply outputs VDC 600...

Страница 100: ...510 option Range 4 20mA IS420 option 1 SHLD Shield connected internally to chassis of the power supply Chassis ground 2 VPROG_ISO Output Voltage Programming input 0 5V 0 10V 4 20mA 3 IPROG_ISO Output...

Страница 101: ...ources to the desired levels and turn the power supply ON 9 4 2 Setting up the power supply for 4 20mA Isolated Programming and Monitoring Perform the following procedure to configure the power supply...

Страница 102: ...cleaning Use low pressure compressed air to blow dust from the unit 10 4 Adjustments and Calibration No internal adjustment or calibration is required There is NO REASON to open the power supply cove...

Страница 103: ...t voltage mode Check current limit and voltage setting 5 2 1 5 2 2 Large ripple present in output Is the power supply in remote sense Is the voltage drop on the load wire high Check load and sense wir...

Отзывы: