27
83532002 Rev H
2.14. J1 Connector
J1-1
ENA_IN
Enable/Disable Dry Contact with J1-14 (ENA_OUT)
J1-2
IF_COM
Isolated Interface Common. Return for SO, PS_OK, and optional IEEE, LAN, USB
interface.
J1-3
IF_COM
Isolated Interface Common. Return for SO, PS_OK, and optional IEEE, LAN, USB
interface.
J1-4
N/C
J1-5
N/C
J1-6
N/C
J1-7
N/C
J1-8
LOC/REM
Input for selecting between Local or Remote Analog programming.
J1-9
VPGM
Input for Remote Analog voltage/resistance programming of the Output Voltage
J1-10
IPGM
Input for Remote Analog voltage/resistance programming of the Output Current
J1-11
VMON
Output Voltage Monitor
J1-12
COM
Control Common for VMON & IMON, CV/CC, LOC/REM signal and P (2-Wire
Parallel method only).
Connected internally to the negative local sense (-LS)
J1-13
CV/CC
Output for Constant Voltage / Constant Current mode indication
J1-14
ENA_OUT
Enable/Disable Dry Contact with J1-1 (ENA-IN)
J1-15
SO
Input for Shut-Off control of the power supply output.
J1-16
PS_OK
Output for indication of the power supply status
J1-17
N/C
J1-18
N/C
J1-19
N/C
J1-20
N/C
J1-21
LOC/REM Signal
Output for indicating if the unit is in Local or Remote Analog programming mode.
J1-22
VPGM_RTN
Return for VPGM J1-9; connected to negative local sense (-LS).
J1-23
IPGM_RTN
Return for IPGM J1-10; connected to negative local sense (-LS) for Vout < 30V.
Floating for models with 30V
≤
Vout
≤
600V.
J1-24
IMON
Output for Current Monitor
J1-25
P
Output for Current Balance in Parallel Option (all methods)