6. To Release Units from Slave Mode
Slave units can be release from their operating mode by using the following
procedure:
a) Depress the
FINE
button for 3 seconds. The Master/Slave configuration
will be displayed on the
CURRENT
display.
b) Select
H1
mode using the
CURRENT
encoder.
c) Depress the
FINE
button again or wait 5 seconds.
d) Turn the AC input power Off to store the new setting(s).
e) After exiting from Slave operation the unit’s parameters will be set to:
•
Programmed Voltage to zero.
•
Programmed Current to zero.
•
UVL to zero volts
•
OVP to its maximum value
•
AST OFF
•
OUT OFF
•
Foldback Protection OFF
•
Locked Front Panel
Figure 6-7: Parallel Connection with Local Sensing (Two-Wire Method)
NOTE
With local sensing it is important to minimize the wire length and resistance. Also,
the positive and negative wire resistance should be as close as possible to each
other to achieve current balance between the power supplies.