Table 4-4: J1 Connector Terminals and Functions
J1 contact
Signal name
Function
Section
J1-1
ENA_IN
Enable/Disable the Power Supply output by dry-contact (short/open)
with ENA_OUT.
J1-2
J1-3
IF_COM
Isolated Interface Common. Return for the SO control, PS_OK signal
and for the optional IEEE, LAN or USB interface.
5.10
J1-4
ι
7
N/C
No Connection
J1-8
LOCAL/
REMOTE
Input for selecting between Local or Remote analog programming of
Output voltage and Output current.
J1-9
VPGM
Input for remote analog voltage/resistance programming of the Output
voltage.
J1-10
IPGM
Input for remote analog voltage/resistance programming of the Output
current.
J1-11
VMON
Output for monitoring the Power Supply Output voltage.
7.6
J1-12
COM
Control Common. Return for VMON, IMON, CV/CC, LOC/REM.
Connected internally to the negative local sense (-LS) potential.
J1-13
CV/CC
Output for Constant-Voltage/Constant-Current mode indication.
J1-14
ENA_OUT
Enable/Disable the power supply output by dry-contact (short/open)
with ENA_IN.
J1-15
SO
Input for Shut-Off control of the power supply output.
J1-16
PS_OK
Output for indication of the power supply status.
J1-17
ι
20
N/C
No Connection.
J1-21
LOC/REM
SIGNAL
Output for indicating if the unit is in Local or Remote analog
programming mode.
J1-22
VPGM_RTN
Return for VPGM input.
Connected internally to the “-LS” potential.
J1-23
IPGM_RTN
Return for IPGM input.
Connected internally to the “-LS” potential for models with Vout < 30V.
Floating for models with 30V
≤
Vout
≤
600V.
J1-24
IMON
Output for monitoring the Power Supply Output current.
7.6
J1-25
P
Output for current balance in parallel operation.