background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

9

mable thermostats, the Superstat allows independent 

adjustments of “offsets” and “differentials” for stages of 

heating and cooling. The offset settings can be viewed 

as setpoints for the second and third stages and are 

programmed in the Superstat in the number of degrees 

(i.e. 1,2,3 ... ) beyond the heating and cooling setpoints 

(temperatures to be maintained). 
The differential for each stage can be viewed as the 

“anticipator” function used in mechanical thermostats.

P + I OPTION 

The SZ1009 also has a P+I option. Without enabling 

this option, stages turn on and off based on temperature 

vs. setpoint alone, as described above. By enabling this 

option, you allow a time factor to be added. This is use-

ful when you are forced to have a large differential due 

to equipment size. At times when the building load is 

low, the temperature could potentially sit a few degrees 

off setpoint for some time. With the time factor added, 

the thermostat would compensate for this, turning on 

the equipment even though the temperature had not 

reached the limits described above. 

SMART RECOVERY 

“Smart Recovery” may be enabled to insure occupant 

comfort while saving money. It takes the building load 

into consideration and ramps the setpoint when going 

from the unoccupied mode to the occupied mode. At the 

beginning of the occupied mode, the occupied setpoint 

will be reached, many times without the need for the 

second stage to come on. This feature is automatically 

disabled when DI3 is set to external time clock.

 DIGITAL 

APPLICATION 

LED 

SERVICE SCREEN 

CONTROL 

SENSOR OR 

 

  INPUT 

 

INDICATION? 

(DI STATUS SCREEN) 

PROVIDED 

DEVICE NEEDED

  DI1 

Fan Proving 

YES 

CHECK FAN,  

YES - turns system mode to "off" 

Differential 

 

  

 

 

 

FAN OK 

— requires manual re-start  

pressure or 

 

 

 

 

 

or FAIL 

(set system to auto) 

current switch 

  DI1 

Equipment 

NO 

OK 

NO 

Dry contact, switch.  Any type  

 

 

Monitoring 

 

(DI1 OPEN or CLOSED) 

 

for monitoring and indication

  DI2 

Service Alert 

YES 

OK or CHECK DI2 

NO 

Dry contact, switch.  Any type  

 

 

 

(DI2 SERVICE OFF or ON) 

 

for monitoring and indication

  DI2 

Monitor with 

NO 

OK 

YES - shifts setpoint by  

Dry contact, switch.

 

 

 

setpoint shift 

 

(DI2 OPEN or CLOSED) 

programmed amount  

 

  DI3 

Filter Service 

YES 

OK or CHECK FILTER 

NO 

Differential pressure switch

 

 

 

 

 

(FILTER OK or CHECK)

  DI3 

External Occupancy Override 

NO 

OK 

YES - switches to occupied mode  

Dry contact such as twist 

 

 

 

 

 

(EXT OVER ON or OFF) 

as long as contact is made 

timer, light switch, etc.

  DI3 

External Time Clock Input* 

NO 

OK 

YES -input overrides thermostat*  

Dry contact; 

 

 

 

 

 

(EXT TIMECLOCK ON or OFF) 

occupancy program 

external time clock

 

 

 

 

 

 

 

(TCS part SL1001a)

Digital Input Summary Table

*See delay on Power-up.

BUILT-IN DELAYS 

The SZ1009 has delays built into the programming 

sequences to protect equipment. The fan has a mini-

mum on and off time of 30 seconds. When the fan is 

in AUTO mode, it will come on 30 seconds before the 

heating or cooling stages are allowed to sequence on, 

and remain on for 2 minutes after the heating or cool-

ing stages sequence off. Each stage has a minimum on 

and off time of two minutes. There is a minimum of two 

minutes between when one stage turns on until the next 

stage is allowed to turn on, as well as when one stage 

turns off until the next stage is allowed to turn off. 

DELAY ON POWER UP 

The SZ1009 has an adjustable delay on power up. When 

several thermostats are used at one location, and the 

power goes out, most thermostats turn all of the units 

back on at the same time on regain of power, creating a 

peak. The thermostat allows you to set a value, in sec-

onds, where no outputs are allowed to turn on for that 

length of time on power up. Setting each unit to a differ-

ent delay allows you to soft start your system, and thus 

prevent this peak.  

Note, this

 

delay is also applied to the 

start of occupied time.

HEAT PUMP MODE 

If HEAT PUMP mode is selected in programming step 5, 

then the SZ1009 will operate in heat pump mode. In 

heat pump mode the Y terminal is is used for both heat-

ing and cooling, and the W terminal is used for control 

of the reversing valve. The reversing valve is set to be 

Open (Unpowered) for cooling by default and can only 

be changed through communications.

Содержание SZ1009

Страница 1: ...ing or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Convertible to heat pump mode in programming Contents Description 1 Features 1 Mou...

Страница 2: ...designations for wir ing See diagram below REMOTE TEMPERATURE SENSOR WIRING Use 18 AWG shielded twisted pair grounded at the sen sor mounting location Sensor wiring runs of up to 250 feet are attainab...

Страница 3: ...outdoor air sensor only Using remote room sensor with both discharge and outdoor air sensors KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user out...

Страница 4: ...K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and CELSIUS for tem perature indication Controller Type Screen Choose Conventional or Heat Pump mode Unit will reset the screen will mome...

Страница 5: ...cool stage 1 Control Mode Screen Enter if you want to control by temperature only P or add a time factor P I Discharge Air Sensor Function Screen Choose whether or not you are using a discharge air s...

Страница 6: ...n on programming through the PC consult your TCS soft ware manual SETTING CLOCK SCHEDULE THROUGH THE KEYPAD To access the clock and schedule screens press the clock setup button To make changes use th...

Страница 7: ...xternal time clock OVERRIDE A timed override is available using the button on the face of the thermostat or through momentary contacts wired into the OVR terminal The amount of time the unit will be o...

Страница 8: ...G LOCKOUT TEMP all cooling stages will be locked out and will remain locked out until the outdoor air temperature rises 2 above the lockout temperature If the outdoor temperature rises above the HEATI...

Страница 9: ...HECK DI2 NO Dry contact switch Any type DI2 SERVICE OFF or ON for monitoring and indication DI2 Monitor with NO OK YES shifts setpoint by Dry contact switch setpoint shift DI2 OPEN or CLOSED programme...

Страница 10: ...e warmer button until the cooling setpoint is greater than the current temperature by one degree The cooling stage s will sequence off The fan will turn off 2 minutes after the last cooling stage 10 G...

Страница 11: ...the service status button simultaneously Service LED is On If the service LED is on it may be for monitoring purposes or it may indicate a critical problem The first monitoring screen which is used t...

Страница 12: ...put are closed PROGRAM DATA This LED will be lit when the thermostat is within the pro gramming or clock setup menus It will blink when the unit is being accessed by a PC Additional monitoring is avai...

Отзывы: