R
2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com
12
PROGRAMMING
The ability to program control parameters is allowed by
factory default. An access code may be required as set in
programming step #38, or access may be denied altogether
using dipswitches described in the setup section.
User’s Guide
Inside the hinged door of the thermostat is the Superstat
™
User’s Guide. This guide is designed to assist the installer
in explaining to the user how to operate their new thermo-
stat, as well as serve as a handy future reference for the
user.
We recommend the installer fill out the appropriate pages in
the User’s Guide and explain to the user how the thermo-
stat operates, what settings may be changed, and how the
time clock schedules are used.
LED Description
Six LEDs on the face allow the occupant to view the current
operating status of the thermostat.
OCCUPIED
This LED will be lit whenever the unit is operating in the
occupied mode.
HEATING
This LED will be lit when any heat output is closed.
COOLING
This LED will be lit when any cooling output is closed.
FAN
This LED will be lit when the fan output is closed.
SERVICE
This LED will be lit when the high or low discharge air
limit has been reached, when the fan interlock has indi-
cated failure, or when the filter service or service input are
closed.
PROGRAM/DATA
This LED will be lit when the thermostat is within the pro-
gramming or clock setup menus. It will blink when the unit
is being accessed by a PC.
Additional monitoring is available by continually pressing
the service key.
Limiting Occupant Access
SETPOINT ADJUSTMENT
The occupant may temporarily change the occupied heat-
ing and cooling set/- 5’F by factory default. This
setpoint change will remain until the end of the current
occupied period, at which time the program reverts to the
setpoints defined in programming. To change the range of
adjustment allowed, see programming step # 21.
OVERRIDE
The occupant has the ability to put the unit into occupied
mode by pressing the override button on the front. By facto-
ry default, the unit will remain in the occupied mode for 180
minutes. This value may be changed from 0 to 255 minutes
in programming step #22.
FAN SWITCHING
The option to allow the occupant to change the occupied
fan mode is allowed by factory default. To lock out access
to fan switching, see programming step #8.
SYSTEM SWITCHING
The option to allow the occupant to change the system
mode is allowed by factory default. To lock out access to
system switching, see programming step #6.
SETTING CLOCK & SCHEDULE
The ability to set the clock and schedule is allowed by fac-
tory default. An access code may be required as set in
programming step #39, or access may be denied altogether
using dipswitches described in the setup section.
Rev. 0313
S
U P E R
S T
A
T
TM
www.tcsbasys.com
C3656_REV5