Checkout & Troubleshooting          

CHECKOUT
Note: 

The fan has a minimum on and off time of 30 sec-

onds.  The heating and cooling stages have a minimum 

on and off time of 2 minutes. 
You may verify the status of heating and cooling stages 

and fan in monitoring screens #5, #6, and #7, which are 

accessed by pressing the SERVICE STATUS button. 
1.  Verify all wiring prior to powering the thermostat.
2. Turn power on.  The thermostat will display a momen-

tary screen with the model number , and then the 

main monitoring screen with the time, day, and current 

temperature. 

3. Press the PROGRAM SETUP button until you reach 

the screen #21 which allows you to set the occupant 

setpoint adjustment limits.  Change this to +/-20 °F 

(11.1 °C).  Press the PROGRAM SETUP button once 

more to store the change.  Then press the SERVICE 

STATUS button once to exit the programming. 

4. Press the FAN SWITCH button to access the fan 

mode and change the mode to AUTO.  Press the 

FAN SWITCH button once more to store the change.   

Press the SYSTEM SWITCH button to access the 

system mode and change the mode to AUTO.  Press 

the SYSTEM SWITCH button once more to store the 

change.  

5. Verify that the thermostat is operating in the occupied 

mode by making sure that the top LED is lit.  If not, 

press the OVERRIDE button.  The LED should light 

up. 

6. Take note of the current temperature reading.  Press 

the WARMER (up) button.  The setpoint adjustment 

screen should now be showing.  Press the WARMER 

button until the heating setpoint is greater than the 

current temperature by at least five degrees.  The fan 

will come on.  The heating stage(s) will sequence on 

after 30 seconds. 

7. Press the cooler (down) button until the heating set-

point is one degree less than the current temperature.  

The heating stage(s) will sequence off.  The fan will 

turn off 2 minutes after the last heating stage. 

8. Press the cooler button until the cooling setpoint is 

less than the current temperature by at least five 

degrees.  The fan will come on.   The cooling stage(s) 

will sequence on after 30 seconds. 

9. Press the warmer button until the cooling setpoint is 

greater than the current temperature by one degree.  

The cooling stage(s) will sequence off.  The fan will 

turn off 2 minutes after the last cooling stage.

10. Go back to programming step #21 and set the set-

point adjust limit back to the desired value. Make any 

other changes in programming, clock, and schedule.  

Set the fan and system modes to their desired set-

tings. 

11. If using remote sensors, verify that the reading is 

correct. If not, see 

Wrong Temperature Display 

in the 

Troubleshooting

 section.

TROUBLESHOOTING
No Display

Check for 24 VAC on terminals “+24” and “-24”.  Check 

ribbon cable connecting the cover to the base for a good 

connection.

Fan Does Not Come On

The fan is on whenever the fan LED is on.  If the 

fan should be on, but the fan LED is off, check 

the fan (FAN SWITCH button) and system modes 

(SYSTEM SWITCH button), and the unoccupied fan 

mode in programming.  If the fan is off but the fan LED 

is on, check wiring.  Short terminals “R” to “G” and see 

if the fan comes on.  This is a check for a mechanical 

relay failure. 

Heating or Cooling Does Not Come On

At least one stage of heating is on whenever the heating 

LED is on, and at least one stage of cooling is on when-

ever the cooling LED is on.  If heating or cooling should 

be on but the heating or cooling LED is off:
1. Check the fan and system switch modes. 
2. Check the heating and cooling setpoints.
3. Check the room temperature to be sure heating or 

cooling should be on. 

4. Check the offsets and differentials.
5. If using outdoor air or discharge air high and low lim-

its, check their values to be sure heating or cooling is 

allowed. 

If heating or cooling is off, but the corresponding SED is 

on, check the wiring.  Short terminals “R” to “W1”,  “Y1”, 

or “G” and see if the heating, cooling, or fan comes on. 

This is a check for a mechanical relay failure. 

Wrong Temperature Display
I

nitially, verify the wiring connections to check for prob-

lems (poor connections, opens, or shorts). If the tem-

perature is at a minimum or maximum reading, check 

that the sensor dipswitch positions are correct as shown 

in the Setup section of this document. Also, verify the 

resistance reading for the sensor in question. A remote 

sensor should read 1080 to 1090 ohms at room temper-

MON

12:00AM 

72F

* SZ1009 * 

 TCS V2.0 (c)

LIMIT SETPOINT

ADJUST  +/-:        05F

Содержание SZ1009

Страница 1: ...ing or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Convertible to heat pump mode in programming Contents Description 1 Features 1 Mou...

Страница 2: ...designations for wir ing See diagram below REMOTE TEMPERATURE SENSOR WIRING Use 18 AWG shielded twisted pair grounded at the sen sor mounting location Sensor wiring runs of up to 250 feet are attainab...

Страница 3: ...outdoor air sensor only Using remote room sensor with both discharge and outdoor air sensors KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user out...

Страница 4: ...K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and CELSIUS for tem perature indication Controller Type Screen Choose Conventional or Heat Pump mode Unit will reset the screen will mome...

Страница 5: ...cool stage 1 Control Mode Screen Enter if you want to control by temperature only P or add a time factor P I Discharge Air Sensor Function Screen Choose whether or not you are using a discharge air s...

Страница 6: ...n on programming through the PC consult your TCS soft ware manual SETTING CLOCK SCHEDULE THROUGH THE KEYPAD To access the clock and schedule screens press the clock setup button To make changes use th...

Страница 7: ...xternal time clock OVERRIDE A timed override is available using the button on the face of the thermostat or through momentary contacts wired into the OVR terminal The amount of time the unit will be o...

Страница 8: ...G LOCKOUT TEMP all cooling stages will be locked out and will remain locked out until the outdoor air temperature rises 2 above the lockout temperature If the outdoor temperature rises above the HEATI...

Страница 9: ...HECK DI2 NO Dry contact switch Any type DI2 SERVICE OFF or ON for monitoring and indication DI2 Monitor with NO OK YES shifts setpoint by Dry contact switch setpoint shift DI2 OPEN or CLOSED programme...

Страница 10: ...e warmer button until the cooling setpoint is greater than the current temperature by one degree The cooling stage s will sequence off The fan will turn off 2 minutes after the last cooling stage 10 G...

Страница 11: ...the service status button simultaneously Service LED is On If the service LED is on it may be for monitoring purposes or it may indicate a critical problem The first monitoring screen which is used t...

Страница 12: ...put are closed PROGRAM DATA This LED will be lit when the thermostat is within the pro gramming or clock setup menus It will blink when the unit is being accessed by a PC Additional monitoring is avai...

Отзывы: