background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

2

POWERING THE SUPERSTAT

Superstats are powered from 24 VAC +/- 20%.
If wiring for communications, dedicated power must be 

used to power the Superstat. Several “S” Series thermo-

stats may be powered from the same transformer, provid-

ed that the transformer has sufficient power. (Superstats 

require 8 VA @ 24 VAC.)

Caution

:  Do not connect to 120 VAC. When multiple 

TCS Basys Controls devices are using a single 

transformer, the polarity of the power wiring 

must be maintained because all TCS devices 

are half-wave rectified and have common 

return paths. 

When the Superstat is used as a stand-alone or wireless 

thermostat without communications, the unit transformer 

may be used to power it.  To do this, install a jumper 

between the “R” and “+24” terminals.  The “24-” terminal 

must then be connected to the common side of the unit 

transformer. 

Wiring                                     

The SZ1009 uses standard terminal designations for wir-

ing.  See diagram below.

REMOTE TEMPERATURE SENSOR WIRING

Use 18 AWG shielded twisted-pair grounded at the sen-

sor mounting location. Sensor wiring runs of up to 250 

feet are attainable if properly shielded wire is used and 

the installation environment is free of electrical noise.  

Sensor wire should be kept at least five feet away from 

line voltage wiring.
The SZ1009 accepts three.  Consult the TS Series 

Temperature Sensor Submittal Data Sheet for a com-

plete listing of packaging and application styles. When 

using TCS Basys Controls three-wire sensors, use the 

black and red leads and either clip or twist off the white 

lead. Make sure that the dip switches are set for the 

sensors you are using.

1

For communication wiring, use twisted,

shielded 22 AWG.  Must be run

separately.  

2

Dry momentary contact.  Must not be

powered

3

24 VAC transformer.

See powering instructions . 

4

Dry contact. Must not be powered.

5

Sensor input wiring 18 AWG,

twisted, shielded pair. 

6

Up to nominal 28 VAC from 

equipment transformer. 

Remote 

Zone/Return

Air Temp

R  W1  

Y1   G

DI3 0VR  T1 T1

+24 –  DI1  DI2

RE

 A 

   

B

T2  T2  T3  T3

6

A

B

R

EF

In Heat Pump Mode 

W1=B/O

Содержание SZ1009

Страница 1: ...ing or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Convertible to heat pump mode in programming Contents Description 1 Features 1 Mou...

Страница 2: ...designations for wir ing See diagram below REMOTE TEMPERATURE SENSOR WIRING Use 18 AWG shielded twisted pair grounded at the sen sor mounting location Sensor wiring runs of up to 250 feet are attainab...

Страница 3: ...outdoor air sensor only Using remote room sensor with both discharge and outdoor air sensors KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user out...

Страница 4: ...K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and CELSIUS for tem perature indication Controller Type Screen Choose Conventional or Heat Pump mode Unit will reset the screen will mome...

Страница 5: ...cool stage 1 Control Mode Screen Enter if you want to control by temperature only P or add a time factor P I Discharge Air Sensor Function Screen Choose whether or not you are using a discharge air s...

Страница 6: ...n on programming through the PC consult your TCS soft ware manual SETTING CLOCK SCHEDULE THROUGH THE KEYPAD To access the clock and schedule screens press the clock setup button To make changes use th...

Страница 7: ...xternal time clock OVERRIDE A timed override is available using the button on the face of the thermostat or through momentary contacts wired into the OVR terminal The amount of time the unit will be o...

Страница 8: ...G LOCKOUT TEMP all cooling stages will be locked out and will remain locked out until the outdoor air temperature rises 2 above the lockout temperature If the outdoor temperature rises above the HEATI...

Страница 9: ...HECK DI2 NO Dry contact switch Any type DI2 SERVICE OFF or ON for monitoring and indication DI2 Monitor with NO OK YES shifts setpoint by Dry contact switch setpoint shift DI2 OPEN or CLOSED programme...

Страница 10: ...e warmer button until the cooling setpoint is greater than the current temperature by one degree The cooling stage s will sequence off The fan will turn off 2 minutes after the last cooling stage 10 G...

Страница 11: ...the service status button simultaneously Service LED is On If the service LED is on it may be for monitoring purposes or it may indicate a critical problem The first monitoring screen which is used t...

Страница 12: ...put are closed PROGRAM DATA This LED will be lit when the thermostat is within the pro gramming or clock setup menus It will blink when the unit is being accessed by a PC Additional monitoring is avai...

Отзывы: