R
2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com
2
POWERING THE SUPERSTAT
Superstats are powered from 24 VAC +/- 20%.
If wiring for communications, dedicated power must be
used to power the Superstat. Several “S” Series thermo-
stats may be powered from the same transformer, provid-
ed that the transformer has sufficient power. (Superstats
require 8 VA @ 24 VAC.)
Caution
: Do not connect to 120 VAC. When multiple
TCS Basys Controls devices are using a single
transformer, the polarity of the power wiring
must be maintained because all TCS devices
are half-wave rectified and have common
return paths.
When the Superstat is used as a stand-alone or wireless
thermostat without communications, the unit transformer
may be used to power it. To do this, install a jumper
between the “R” and “+24” terminals. The “24-” terminal
must then be connected to the common side of the unit
transformer.
Wiring
The SZ1009 uses standard terminal designations for wir-
ing. See diagram below.
REMOTE TEMPERATURE SENSOR WIRING
Use 18 AWG shielded twisted-pair grounded at the sen-
sor mounting location. Sensor wiring runs of up to 250
feet are attainable if properly shielded wire is used and
the installation environment is free of electrical noise.
Sensor wire should be kept at least five feet away from
line voltage wiring.
The SZ1009 accepts three. Consult the TS Series
Temperature Sensor Submittal Data Sheet for a com-
plete listing of packaging and application styles. When
using TCS Basys Controls three-wire sensors, use the
black and red leads and either clip or twist off the white
lead. Make sure that the dip switches are set for the
sensors you are using.
1
For communication wiring, use twisted,
shielded 22 AWG. Must be run
separately.
2
Dry momentary contact. Must not be
powered
3
24 VAC transformer.
See powering instructions .
4
Dry contact. Must not be powered.
5
Sensor input wiring 18 AWG,
twisted, shielded pair.
6
Up to nominal 28 VAC from
equipment transformer.
Remote
Zone/Return
Air Temp
R W1
Y1 G
DI3 0VR T1 T1
+24 – DI1 DI2
RE
F
A
B
T2 T2 T3 T3
6
A
B
R
EF
In Heat Pump Mode
W1=B/O