User Manual of Solar Intelligent Energy System (SIES)
TBB Power Confidential Page
36
of
66
Table 24 Location of AGS
Model of Smart Box
Location of AGS terminal block
SMB-30L60, SMB-30M60, SMB-40S60
Terminal panel of Smart Box
SMB-50M60, SMB-80S60, SMB-80S60x2
Central panel of Energier Pro
The maximum
current which AGS’s built-in dry contact allows:
230Vac
: 2A
12Vdc / 24Vdc / 36Vdc
: 2A
Please refer to the
user manual of generator, connect “GEN ON” or” GEN STARTNC, COM, NO” to
the remote terminal of generator, for the purpose of controlling the
“Start” and “Stop” of generator.
Please refer to the Chapter 7 for the introduction of how to setup the conditions of
“Start” and “Stop”
of generator.
Basically, there are two ways of automatically starting generator:
Two wires
: needs
only one relay to control the “Start” and “Stop” of generator. Please refer to
following Figure 26.
Figure 26 Two wires: Automatic Generator Start
Three wires:
needs two relays to control the generator. Relay 1 controls
the “ON” and “OFF” of
generator. Relay 2 control the
“Start” and “Stop” of generator. Please refer to following Figure
27.
Figure 25 Automatic Generator Start (AGS)