6
DIP-SW
Function
Description
1
EMERGENCY
ON
Enables opening with always closed program.
OFF
Disables opening with always closed program.
2
DISABLED ACCESS
FUNCTION
ON
Enables the disabled access function (activates the semi-au-
tomatic opening mode)
The opening of the door is activated only by the START command
(term. 19-20).Important: automatic closing and parking opening
voltage are activated, while PUSH AND GO, parking closing voltage
and radar are deactivated.
OFF
Disables the disabled access function (activates the automatic
opening mode).
Normal operation.
3
BATTERY
MONITORING
ON
If there is no voltage, the automation performs the manoeu-
vres normally. If the battery is flat, the board switches off.
OFF
If there is no voltage, the automation performs the ma-
noeuvres normally. Before the battery is fully discharged, it
performs an opening manoeuvre.
4
OPENING IN
BATTERY
ON
In the event of a power failure, the automation opens and re-
mains open until the mains voltage is restored (DIP7 must be
OFF)
OFF
In the event of a power failure, the automation performs the
maneuvers normally.
5
TCA
INCREASE
ON
With a high flow of passages, the automatic closing time is
automatically increased.
OFF
Function disabled, the automatic closing time remains un-
changed.
10
DISABLE SENSORS
ON
Activation and safety sensors deactivated.
2 WAY
OFF
Activation and safety sensors activated.
11
ENTRY 19 OPENS
/ PP
ON
Enables the Step-by-Step function on input 19.
OFF
Enables the OPENING function on input 19.
12
LOW ENERGY
ON
Enables the low energy function (reduced speeds)
OFF
Disables the low energy function (normal speeds)
14
PUSH ON FCC
ON
Enables push function on closing limit switch
OFF
Disables push function on closing limit switch
15
INSIDE SENSOR
TEST
ON
Enables internal sensor test – the test is carried out on the
input, PICTURE1
OFF
Disables the test on the input, PICTURE1
16
OUTSIDE SENSOR
TEST
ON
Enables external sensor test – the test is carried out on the
input, PICTURE2
OFF
Disables the test on the input, PICTURE2