10

Vmin.CL 

adjusts the minimum closing speed while acquiring the run (setup) - In nor-

mal run, it will be the minimum speed before stopping.

 

Note. The setup procedure can automatically increase the set value in case of an  

 

automation with high mechanical friction.

VsetupOP 

adjusts the opening setup speed.

VsetupCL 

adjusts the closing setup speed.

EndApp.OP 

adjusts the section travelled at minimum speed when opening, before

 

stopping on the opening limit switch.

EndApp.CL 

adjusts the section travelled at minimum speed when closing, before stop-

ping on the closing limit switch.

Limit.OP 

adjusts the stopping point when opening (opening limit switch).

Limit.CL 

adjusts the stopping point when closing (closing limit switch).

Accel.OP 

adjusts the acceleration time when opening.

Accel.CL 

adjusts the acceleration time when closing. 

Power.OP 

Adjusts the opening force.

Power.CL 

Adjusts the closing force.

Breaking.OP 

sets the opening slowdown duration.

Breaking.CL 

sets the closing slowdown duration.

Park.OP 

adjusts the parking voltage with the door open.

Park.CL 

adjusts the parking voltage with the door closed.

Push&Go 

adjusts the manual push for automatic opening.

Ssoa.OP 

Adjusts the operating area of   the safety sensor in opening.

Parameters  

  Timings

TCA  

adjusts the automatic closing time.

TRA.OP 

adjusts the leaf delay time in opening (for double leaf MASTER/SLAVE)

TRA.CL 

adjusts the leaf delay time in closing (for double leaf MASTER/SLAVE)

Timeout 

adjusts the maximum time necessary to carry out a manoeuvre. If exceeded 

without the automation reaching a limit switch, the DC18 board will issue a 

“timeout” alarm (error 5R - automation timeout).

T_Exit 

adjusts the exit time with the “always locked” programme. During this time, the 

internal sensor remains enabled to allow exiting. Once exceeded, the automa-

tion will remain locked closed.

T_Restore  

adjusts the reset time after an error. Following an error/alarm, when the reset 

time expires, the automation will perform an automatic realignment at low 

speed to get to a known position.

T_Elock  

adjusts the activation time of the electric lock.

T_WElok 

It adjusts the leaf opening delay time when an electric lock is activated in conti-

nuous mode.

Impostazioni  

 

 

Technical parameters

Call TAU technical service to modify these parameters.

Содержание T-SIDETD

Страница 1: ...INSTALLATION GUIDE GUIDA ALL INSTALLAZIONE IT Istruzioni originali T SIDETD D MNL0TSIDETD 25 05 2023 Rev 09...

Страница 2: ...ed by qualified personnel in compliance with current laws regulations and directives When designing its products TAU observes all applicable standards please see the at tached decla ration of conformi...

Страница 3: ...e main menu Symbol Description Symbol Description Menu Power ok Down Recom mended stroke seutp Up Manual operating on Exit select work programs Enter Error alert Symbols shown in the inputs diagnostic...

Страница 4: ...sible to enable some options on the work pro grammes A No function B OPEN key key to open the door In order to assign the required function to the work programme it is first of all necessary to assign...

Страница 5: ...L sets the closing slowdown duration TCA adjusts the automatic closing time TRA OP adjusts the leaf delay time in opening for double leaf MASTER SLAVE TRA CL adjusts the leaf delay time in closing for...

Страница 6: ...ure the automation opens and re mains open until the mains voltage is restored DIP7 must be OFF OFF In the event of a power failure the automation performs the maneuvers normally 5 TCA INCREASE ON Wit...

Страница 7: ...MENU Options Language Change and select the desired language Language UsePasswordL0 ChangePswL0 UsePasswordL1 Italiano English Deutsch Francais Options Use password L0 Enables Disables the use of the...

Страница 8: ...edpassword successfully OPTIONS PERSONALIZZA TASTO P2 Through the Set key P2 function it is possible to enable some options on the work pro grammes A No function B OPEN key key to open the door In ord...

Страница 9: ...ETTINGS This menu gathers all the advanced parameters necessary to adjust the automation in detail To access it it will be necessary to press the keys P3 and P4 at the same time When changing one or m...

Страница 10: ...oor open Park CL adjusts the parking voltage with the door closed Push Go adjusts the manual push for automatic opening Ssoa OP Adjusts the operating area of the safety sensor in opening Parameters Ti...

Страница 11: ...ters Update procedure Setup procedure Performsthesetup ofmotionpro le Con rm Options Reset Parameters It allows the user to restore all parameters to factory conditions The basic parameters will be se...

Страница 12: ...tacle or check whether the leaf runs smo othly or not If necessary increase the power values through parameters Power OP and Power CL R3 No mains vol tage The automation wor ks in battery Check magnet...

Страница 13: ...sliding of the door If necessary increase the force values with the parame ters Power OP and Power CL G5 Encoder fault motor 2 Encoder fault check connections Make sure that the motor is moving that t...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...0376 info tauitalia com www tauitalia com Foglietto illustrativo CARTA Raccolta differenziata Segui le indicazioni del tuo comune N B togliere i punti metallici Instruction leaflet PAPER Waste separat...

Отзывы: